| 2014-02-03 14:39:38 | PLUMBING PLAN REVIEW |
| | PERMIT: 14011417 |
| | MASTER:11120073 |
| | ADD: 700 N CONGRESS |
| | CONT: T H BUILDING CORP LLC |
| | TEL: (386)315-0587 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: MON. FEB. 03/2014 |
| | ACTION: DENIED |
| | |
| | 1) THERE ARE CONCERNS OF STAGNATION OF THE POTABLE |
| | WATER IN THE DRINKING WATER STORAGE TANK. THE SUBMITTED |
| | PLANS OF A 6,000GALLON TANK, 6'-0" X 30'-0" WENDLAND |
| | HORIZONTAL HYDROPNEUMATIC TANK INDICATE NOTE (F) A |
| | INLET IN THE LEFT END AND (G) THE OUTLET LOCATED IN THE |
| | CENTER OF THE 30'-0" TANK. THE TANK DOES NOT SHOW ANY |
| | NOTES THAT WILL ALLOW FOR THE WATER TO FLOW PAST THE |
| | MID-POINT IN THE TANK. SHEET C-11 SHOWS THE DOMESTIC |
| | WATER TANK WITH A INLET IN ONE END AND THE OUTLET IN |
| | THE OTHER END, THE PLUMBING SHEET P-7.01 NOTE # 5 |
| | INDICATES THE BASIS OF THE TANK DESIGN IS A VICKERY |
| | WHICH ALSO WAS NOT PROVIDED. |
| | |
| | THE UNKNOWN OF HOW THE WATER IS GOING TO BE KEPT MOVING |
| | SO THERE ARE NO EDDIES AND OR DEAD ENDS WHERE THE WATER |
| | WOULD BECOME STAGNENT IS OF GREAT CONCERN. THE |
| | SUBMITTED DIAGRAM DOESN'T SHOW ANY JETTING OF WATER TO |
| | FORM CIRCULATION PATTERNS OR OTHER DEVICES THAT WOULD |
| | CIRCULATE THE WATER TO KEEP A BIOFILM LAYER FROM |
| | FORMING IN THE DEAD END AREA. |
| | |
| | THE OTHER CONCERN IS THE STRAIFICATION OF THE WATER THE |
| | WARMER WATER GOING TO THE TOP OF THE TANK AND THE |
| | COOLER WATER SETTLING TO THE BOTTOM HOW WILL THE HOW |
| | WILL THE FILL AND DRAW OF THE WATER HELP TO KEEP THE |
| | FLOW OF THE WATER WITHIN THE TANK CONSTANT? |
| | |
| | 2010 FBC-PLUMBING 604.1 GENERAL. THE DESIGN OF THE |
| | WATER DISTRIBUTION SYSTEM SHALL CONFORM TO ACCEPTED |
| | ENGINEERING PRACTICE. |
| | |
| | 2) THE CIVIL PLANS AND PLUMBING SHEET P-7.01 BOTH |
| | INDICATE THIS TANK TO BE BURRIED BENEATH THE GROUND |
| | WITH A 36" DIAMETER MANWAY W/ TRAFFIC DUTY MANHOLE |
| | COVER & RIM. THE CONCERN IS ANY OPENING ON A WATER TANK |
| | MUST BE PROTECTED AGAINST CONTAMINATION THE PLANS DO |
| | INDICATE A 12" ROOF DRAINAGE PIPE AS WELL AS (2) |
| | CISTERNS ON THE SAME SIDE OF THE BUILDING HOW WILL THE |
| | RAIN RUN OFF BE TAKEN CARE OF TO KEEP IT FROM GOING |
| | INTO THE 36 INCH MANHOLE COVER ? |
| | 2010 FBC-PLUMBING 606.5.8 PROHIBITED LOCATION OF |
| | POTABLE SUPPLY TANKS. POTABLE WATER GRAVITY TANKS OR |
| | MANHOLES OF POTABLE WATER PRESSURE TANKS SHALL NOT BE |
| | LOCATED DIRECTLY UNDER ANY SOIL OR WASTE PIPING OR ANY |
| | SOURCE OF CONTAMINATION. |
| | |
| | 3) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE FOOT |
| | VALVE ON THE END OF THE SUCTION PIPE. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |