| 2014-02-12 17:35:38 | FAILED |
| | |
| | 1) THE CITYPLACE MANAGEMENT STAMP IS REQUIRED ON THE |
| | PLANS. |
| | |
| | 2) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT THE |
| | AWNING COLORS, COPY AND/OR LOGO SHALL BE APPROVED BY |
| | CITYPLACE RETAIL IN WRITING. |
| | |
| | 3) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT AWNINGS |
| | SHALL PROVIDE A MINIMUM OF EIGHT (8) FEET OF CLEARANCE |
| | BETWEEN THE FLOOR AND THE LOWEST POINT OF THE AWNING. |
| | THE TAKO/TYKO PLANS SHOW COMPLIANCE WITH THIS STANDARD, |
| | BUT THE STRUCTURAL DRAWINGS SHOW 7'6" TO THE GROUND. |
| | CORRECT THE DRAWINGS. |
| | |
| | 4) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT AWNINGS |
| | ON THE STREET LEVEL SHALL PROJECT FOUR (4) FEET FROM |
| | THE BUILDING FACADE, UNLESS OTHERWISE APPROVED BY |
| | CITYPLACE RETAIL IN WRITING. AWNING TYPE 1 AND 2 DO NOT |
| | MEET THIS STANDARD. |
| | |
| | 5) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT ALL |
| | AWNINGS ON STREET LEVEL MUST HAVE AN EIGHT (8) INCH |
| | VERTICAL VALANCE ALONG THE FRONT OF THE AWNING. THE |
| | VALANCE MUST BE PROVIDED WITH CONCEALED WEIGHT TO |
| | PREVENT EXCESSIVE MOVEMENT IN HIGH WINDS. AWNING TYPE 1 |
| | DOES NOT MEET THIS STANDARD. |
| | |
| | 6) PLEASE EXPLAIN WHERE THE 7 INCH DEEP SECTION SHOWN |
| | ON AWNING TYPES 2 AND 3 ARE LOCATED. |
| | |
| | 7) AWNING TYPES 1 AND 2 ARE MISLABELED ON THE |
| | ARCHITECTURAL AND STRUCTURAL PLANS. |
| | |
| | 8) 2 FULL SETS OF THE STRUCTURAL PLANS WERE NOT |
| | INCLUDED WITH THE APPLICATION. |
| | |
| | THESE COMMENTS HAVE BEEN SENT TO CARLOS BERNAL OF |
| | CITYPLACE. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
| 2014-01-27 14:59:39 | 1/27/14 - ZONING RECEIVED. SENT TO ES FOR REVIEW. LL |