| Date |
Text |
| 2014-01-23 17:33:41 | PLUMBING PLAN REVIEW |
| | PERMIT: 14011387 |
| | ADD: 1793 PALM BEACH LAKES # W407 |
| | CONT: TO BE DETERMINED |
| | TEL: (561)373-3902 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURSDAY JAN. 23/2014 |
| | ACTION: DENIED |
| | |
| | 1) WITH THE OCCUPANT LOAD FOR THIS TENANT, 2 RESTROOMS |
| | ARE REQUIRED, ONE OF THE RESTROOMS CAN BE COUNTED WITH |
| | THE COMMON RESTROOMS IN BUILDING J09, THE SECOND |
| | RESTROOM WILL STILL NEED TO COMPLY WITH 2010 FBC-P |
| | 403.3.1 ACCESS. |
| | THE ROUTE TO THE PUBLIC TOILET FACILITIES REQUIRED BY |
| | SECTION 403.3 SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| | ROOMS OR CLOSETS. ACCESS TO THE REQUIRED FACILITIES |
| | SHALL BE FROM WITHIN THE BUILDING OR FROM THE EXTERIOR |
| | OF THE BUILDING. ALL ROUTES SHALL COMPLY WITH THE |
| | ACCESSIBILITY REQUIREMENTS OF THE FLORIDA BUILDING |
| | CODE, ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO |
| | THE REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE |
| | BUILDING IS OCCUPIED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |