| 2014-01-25 11:19:35 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. REVISE FLOOR PLAN TO PROVIDE THE FOLLOWING |
| | INFORMATION FOR THE TWO BEDROOMS WITH WINDOWS H, I, J; |
| | FBC R310, FBC EB 604.1 . THE CLEAR OPENING CANNOT BE |
| | REDUCED BY MORE THAN 5%: |
| | |
| | REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW |
| | IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG? |
| | |
| | REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING |
| | DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH |
| | EXISTS WHEN THE WINDOW IS FULLY OPEN. |
| | |
| | REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING |
| | DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE |
| | MANUFACTURER. |
| | |
| | THERE IS A NOTE ON THE PLAN REGARDING EMERGENCY EGRESS |
| | WINDOWS REQUIREMENTS, BUT ENGINEER SPECIFIES BEDROOM |
| | WINDOWS WHICH DO NOT COMPLY WITH THIS REQUIREMENTS. |
| | PURPOSE OF THE "EMERGENCY EGRESS WINDOWS" NOTE IS NOT |
| | CLEAR. ALSO GROUND FLOOR REQUIREMENT OF 5.7 FEET |
| | EXCEEDS MINIMUM CODE REQUREMENT. IT IS ACCEPTABLE TO |
| | EXCEED MINIMUM CODE REQUIREMENTS BUT IT DOES NOT APPEAR |
| | THAT THE WINDOWS MEET THIS REQUIREMENT. WINDOW |
| | DIMENSION INDUSTRY STANDARD IS TO BE EXPRESSED AS WIDTH |
| | X HEIGHT. ARE THE WINDOW SIZES NOTED INCORRECTLY? |
| | |
| | 2. VALUE IS TOO LOW. VALUE IS TO INCLUDE LABOR, |
| | MATERIALS, OVERHEAD, PROFIT, ENGINEERING FBC 109. |
| | PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. |
| | |
| | 3. TWO COMPLETE SETS OF PLANS REQUIRED. ONLY ONE SET OF |
| | PRODUCT APPROVALS PROVIDED FBC 107. FAILURE TO PROVIDE |
| | TWO COMPLETE SETS MAY RESULT IN ADMIN/COPY FEES |
| | ASSESSED. |
| | |
| | 4. HORIZONTAL ROLLER PRODUCT APPROVALS SUBMITTED, BUT |
| | WINDOW AND DOOR SCHEDULE DOES NOT INCLUDE ANY |
| | HORIZONTAL ROLLER WINDOWS. SCOPE NOT CLEAR; FBC 107. |
| | |
| | |
| | |