2014-01-24 15:08:332010 FBC
  
 DENIED BY BUILDING
  
 1) SPECIFY THE DESIGN DATA ON THE PLANS. THE STRUCTURE
 IS LOCATED IN A 170 MPH VULT WIND-SPEED AND THE
 EXPOSURE CATEGORY IS C. FBCR 301.2.1.1
  
 2) SPECIFY THE REQUIRED DESIGN PRESSURES FOR THE NEW
 EXTERIOR DOOR OPENING. FBC R301.2.1
  
 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE NEW
 EXTERIOR DOOR. DCA RULE 9N-3
  
 4) SHOW COMPLIANCE WITH FBC R318 FOR TERMITE PROTECTION
 AT NEW SLAB.
  
 5) PROVIDE A DETAIL OF THE TIE BEAMS AT THE NEW CBS
 WALLS. SPECIFY THE SIZE OF THE BEAM, THE SIZE AND
 NUMBER OF HORIZONTAL REINFORCING BARS. CITY AMENDMENTS
 107.2.1.
  