| Plan Review Notes For Permit 14011292 |
| Permit Number |
14011292 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-25 16:17:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW AND DOOR | | | LOCATIONS, SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE | | | EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE | | | FOR BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING | | | CANNOT BE REDUCED BY MORE THAN 5%. | | | | | | 2. SCOPE NOT CLEAR. APPLICATION IS FOR WINDOWS AND | | | DOORS, BUT A ROOFING PRODUCT APPROVAL WAS SUBMITTED. | | | | | | 3. VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD, | | | PROFIT, FBC 109. PROVIDE A COPY OF THE CONTRACT FOR | | | THIS JOB. | | | | | | |
|