| Plan Review Notes For Permit 14011279 |
| Permit Number |
14011279 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-25 13:49:33 | FUEL GAS PLAN REVIEW | | | PERMIT: 14011279 | | | ADD: 816 ARDMORE RD | | | CONT: APEX GAS CONTRACTORS | | | TEL: (561)202-7873 | | | | | | 2010 FLORIDA FUEL GAS CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: SATURDAY JAN. 25/ 2014 | | | ACTION: DENIED | | | | | | 1) SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2010 FUEL GAS SEC. 402.2. | | | | | | 2) 503.4.2 SPECIAL GAS VENTS. SPECIAL GAS VENTS SHALL | | | BE LISTED AND INSTALLED IN ACCORDANCE WITH THE SPECIAL | | | GAS VENT MANUFACTURER?S INSTALLATION INSTRUCTIONS. | | | TO PROVIDE THE MINIMUM PROXIMATY OF THE APPLIANCE TO | | | WINDOWS, DOORS, INSIDE CORNERS AND ROOF OVER HANGS. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|