| Plan Review Notes For Permit 14011236 |
| Permit Number |
14011236 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-26 10:17:56 | NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME | | | POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET. | | | NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES | | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | | FEET OF EACH SLEEPING ROOM. | | | NEC 210.63 - PROVIDE A GFI SERVICE OUTLET WITHIN 7.5' | | | OF THE RELOCATED CONDENSER UNIT. | | | |
|