| Plan Review Notes For Permit 14011176 |
| Permit Number |
14011176 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2014-08-21 08:58:24 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE NON-ENGINEERED FLOOD OPENINGS SPECIFIED ON | | | SHEETS A-1 AND A-4 OF THE PLANS ARE ALL LOCATED ON THE | | | SAME EXTERIOR WALL. FBCR322.2.2(2)(2.1) REQUIRES A | | | MINIMUM OF TWO OPENINGS ON DIFFERENT SIDES OF EACH | | | ENCLOSED AREA. PROVIDE OPENINGS ON ONE OF THE OTHER | | | EXTERIOR WALLS. ONLY THE "NET OPEN AREA" OF THE | | | NON-ENGINEERED OPENINGS CAN BE COUNTED TOWARD THE | | | REQUIRED FLOOD OPENING AREA. THE MEASUREMENT OF THE NET | | | OPEN AREA MUST TAKE INTO CONSIDERATION ANY COVERINGS | | | THAT HAVE SOLID OBSTRUCTIONS, SUCH AS GRILLS, FIXED | | | LOUVERS OR FACEPLATES. | | | | | | 2) THE ROOFING PRODUCT APPROVALS THAT WERE SUBMITTED | | | ARE FOR A CONCRETE DECK AND THIS PROJECT HAS A PLYWOOD | | | ROOF DECK. THE PRODUCT APPROVALS ARE REQUIRED TO BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD. SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR | | | THE ROOFING MATERIALS THAT WILL BE USED AS REQUIRED BY | | | DCA RULE 9N-3. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|