| Plan Review Notes For Permit 14011176 |
| Permit Number |
14011176 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-07-03 11:37:04 | DATE: 7/3/2014 | | | PROJECT: | | | PERMIT#: | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 3RD ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) THE SMOKE/CARBON MONOXIDE DETECTORS SHOWN ON THE | | | LANDING APPEAR TO BE OUT IN THE OPEN. NOT ONLY ARE | | | THESE DEVICES NOT LISTED FOR OUTDOOR USE, BUT THEY ARE | | | NOT NEEDED. | | | 2) A CORRECTION/ADDITION TO "NOTE 8" TO INCLUDE THE NEC | | | 314.27 REQUIREMENT STATING THAT THESE BOXES SHALL BE | | | LISTED TO SUPPORT 50#. | | | 3) ADDITIONAL OUTLETS REQUIRED IN THE BEDROOMS TO MEET | | | THE SPACING CRITERIA OF NEC 210.52 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|