Plan Review Notes
Plan Review Notes For Permit 14011175
Permit Number 14011175
Review Stop E
Sequence Number 2
Notes
Date Text
2014-02-05 16:02:12REVISE LOAD CALCULATION TO ACCOUNT FOR ADDED RECEPTACLE
 LOAD AND ASSURE LIGHTING LOAD IS CALCULATED AT 3.5
 VOLT-AMPS/SF, PER NEC 220.12. REVISE PANEL SCHEDULE AS
 NEEDED. THIS WAS INDICATED IN FIRST REVIEW. NEW TO THIS
 REVIEW, SHOW THE SIGN CIRCUIT AND PROVIDE EXTERIOR
 LIGHTING CONTROLS PER FBC-EC 505.2.4
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  