| Plan Review Notes For Permit 14011172 |
| Permit Number |
14011172 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-02-05 15:57:52 | REVISE LOAD CALCULATION TO ACCOUNT FOR ADDED RECEPTACLE | | | LOAD AND ASSURE LIGHTING LOAD IS CALCULATED AT 3.5 | | | VOLT-AMPS/SF, PER NEC 220.12. REVISE PANEL SCHEDULE AS | | | NEEDED. THIS WAS INDICATED IN FIRST REVIEW. NEW TO THIS | | | REVIEW, SHOW THE SIGN CIRCUIT AND PROVIDE EXTERIOR | | | LIGHTING CONTROLS PER FBC-EC 505.2.4 | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|