| 2014-04-15 15:13:52 | PLUMBING PLAN REVIEW |
| | PERMIT: 14011102 |
| | ADD: 1715 PALM BEACH LAKES |
| | RED ROBIN GOURMET BURGERS & BREWS |
| | CONTRACTOR: TO BE DETERMINED |
| | CONTACT: A & J |
| | TEL: (561) 373-3902 KARI |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED |
| | APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: TUESDAY APRIL 15/2014 |
| | ACTION: DENIED |
| | |
| | 1) NOTICE ONLY: 2010 FBC-PLUMB.315.1 REQUIREMENTS. |
| | PUBLIC FOOD SERVICE ESTABLISHMENTS AND FOOD |
| | ESTABLISHMENTS, AS DEFINED IN CHAPTER 381 FLORIDA |
| | STATUTES, CHAPTER 500 FLORIDA STATUTES AND CHAPTER 509 |
| | FLORIDA STATUTES, SHALL COMPLY WITH THE APPLICABLE CODE |
| | REQUIREMENTS FOUND IN THE FLORIDA BUILDING CODE, |
| | BUILDING, CHAPTER 4, SPECIAL DETAILED REQUIREMENTS |
| | BASED ON USE AND OCCUPANCY. PLEASE SEE DBPR WEBSITE FOR |
| | ADDITIONAL INFO: |
| | HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/LICENSING/ |
| | PLANREVIEWINDEX.HTML |
| | |
| | 2) 2ND REVIEW THE REQUEST FOR REVIEW UNDER 2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 104.11 ALTERNATE MATERIALS, DESIGN AND METHODS OF |
| | CONSTRUCTION IS BEING REVIEWED BY THE BUILDING OFFICIAL |
| | AND DIRECT WRITTEN RESPONCE FROM HIM. |
| | PLEASE NOTE GREASE INTERCEPTORS REQUIRE A SEPERATE |
| | PERMIT FOR RECORD RETENTION AND ENFORCEMENT OF THE |
| | CITIES FOG PROGRAM TO KEEP FROM HARMING THE CITIES |
| | SANITARY SYSTEM. PLEASE PROVIDE THE SIZE OF THE GREASE |
| | INTERCEPTOR, LOCATION AND PROVIDE THE CALCULATION FOR |
| | SIZING OF THE GREASE INTERCEPTOR. |
| | GREASE INTERCEPTORS THAT ARE SIZED, CONSTRUCTED AND |
| | APPROVED IN ACCORDANCE WITH RULE 64E-6, FLORIDA |
| | ADMINISTRATIVE CODE AND THAT ARE LOCATED OUTSIDE THE |
| | BUILDING SHALL USE THE FORUMULA FOUND IN FBC-P TABLE |
| | 1003.5.1 FOR RESTARAUNTS. THIS CAN BE SUBMITTED UNDER |
| | THIS REVIEW, NOTED FOR A TURN AROUND PERMIT WHEN |
| | APPLIED FOR. |
| | |
| | 3) 2ND REQUEST. THE GAS REVIEW IS CURRENTLY BEING |
| | COMPLETED UNDER THE PLUMBING PLAN REVIEW. IF THIS WAS |
| | THE ONLY ISSUE WITH THE PLUMBING PLAN REVIEW IT WOULD |
| | BE PULLED OUT AND TO THE SEPERATE FUEL GAS REVIEW. |
| | THESE COMMENTS WILL REAPPEAR UNDER THE HEADING OF THE |
| | GAS REVIEW. SEPARQATE PERMIT FOR GAS IS REQUIRED |
| | BECAUSE OF THE INSPECTION CODES ARE NOT PART OF A |
| | PLUMBING PERMIT, |
| | |
| | 3A) SHEET P3.2 DETAIL 1A A OVERALL GAS RISER DIAGRAM |
| | INDICATES THE DESIGN TO BE NATURAL GAS, < THAN A 2 LB |
| | SYSTEM (1/2 LB) WITH A TOTAL OVER DISTANCE OF 125 FEET |
| | AND A PRESSURE DROP OF 0.3 IN W.C. AND SPECIFIC GRAVITY |
| | OF 0.60. |
| | |
| | 3A)(1) WHEN READING THE LENGTH OF 125 FEET FOR 3 INCH |
| | BLACK PIPE THE TABLES INDICATE 2,190 CFH WHERE AS THE |
| | PLANS TOTAL LOAD IS 2,257 CFH WHICH IS LOW. |
| | |
| | 3A)(2) THE SAME DETAIL P3.2 DETAIL 1A SHOWS A 3 INCH |
| | BRANCH OFF TO THE RTU UNITS ON THE ROOF. WHERE THIS T |
| | OCCURS THE PLANS INDICATE THE SIZE OF THE BLACK STEEL |
| | PIPE TO BE REDUCED TO 2 INCH (817 CFH, 125'). PLEASE |
| | REVIEW TABLE 402.4(1) FOR 125 FT, IT IS ONLY GOOD FOR |
| | 777 CFH ON A 1/2 LB SYSTEM |
| | |
| | 3A)(3) PLEASE PROVIDE A DETAIL FOR WHERE THE GAS LEAVES |
| | THE METER, IT APPEARS TO BE A MANIFOLD WITH A 3 INCH |
| | AND A 1 1/4 INCH PIPES LEAVING THE MANIFOLD. PLEASE |
| | PROVIDE WHAT SIZE PIPING THE MANIFOLD WILL BE CREATED |
| | FROM. ADDITIONAL INFORMATION IS REQUIRED.107.2.1.3. |
| | |
| | 3A)(4) SHEET P3.2 DETAIL 1A NOTES INCLOSED BY A BOX |
| | INDICATE THE PIPE TO BE BLACK STEEL PIPE AND THE TABLE |
| | 402.4(1) ALSO CONFIRMS SCHEDULE 40 METALLIC PIPE. |
| | SHEET P3.1 DETAIL GAS DETAIL AT COOK LINE INDICATES AS |
| | AN ALTERNATE TO WELDED FITTINGS TRACPIPE BY OMEGAFLEX |
| | MAY BE USED. TWO ISSUES WITH THIS. |
| | A) 2010 FBC-FUEL GAS 404.3 DOES NOT ALLOW FOR FITTINGS |
| | OR UNIONS WITH IN WALLS. STEEL PIPE WOULD BE ALLOWED |
| | WITH WELDS BUT THE TERM ALTERNATE IS NOT ALLWED. |
| | B) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" |
| | OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 4) PLEASE PROVIDE COMPLIANCE WITH: 411.1.1 COMMERCIAL |
| | COOKING APPLIANCES. |
| | COMMERCIAL COOKING APPLIANCES INSTALLED ON CASTERS AND |
| | APPLIANCES THAT ARE MOVED FOR CLEANING AND SANITATION |
| | PURPOSES SHALL BE CONNECTED TO THE PIPING SYSTEM WITH |
| | AN APPLIANCE CONNECTOR LISTED AS COMPLYING WITH ANSI |
| | Z21.69 OR IN ACCORDANCE WITH ITEM 1 OR 3 OF SECTION |
| | 411.1. |
| | |
| | 411.1.2 PROTECTION AGAINST DAMAGE. |
| | CONNECTORS AND TUBING SHALL BE INSTALLED SO AS TO BE |
| | PROTECTED AGAINST PHYSICAL DAMAGE. |
| | |
| | 411.1.3 CONNECTOR INSTALLATION. |
| | APPLIANCE FUEL CONNECTORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS AND |
| | SECTIONS 411.1.3.1 THROUGH 411.1.3.4. |
| | |
| | 411.1.3.1 MAXIMUM LENGTH. |
| | CONNECTORS SHALL HAVE AN OVERALL LENGTH NOT TO EXCEED 6 |
| | FEET (1829 MM). MEASUREMENT SHALL BE MADE ALONG THE |
| | CENTERLINE OF THE CONNECTOR. ONLY ONE CONNECTOR SHALL |
| | BE USED FOR EACH APPLIANCE |
| | |