2014-04-15 15:13:52PLUMBING PLAN REVIEW
 PERMIT: 14011102
 ADD: 1715 PALM BEACH LAKES
 RED ROBIN GOURMET BURGERS & BREWS
 CONTRACTOR: TO BE DETERMINED
 CONTACT: A & J
 TEL: (561) 373-3902 KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED
 APRIL 25/2013.
  
 2ND REVIEW
 DATE: TUESDAY APRIL 15/2014
 ACTION: DENIED
  
 1) NOTICE ONLY: 2010 FBC-PLUMB.315.1 REQUIREMENTS.
 PUBLIC FOOD SERVICE ESTABLISHMENTS AND FOOD
 ESTABLISHMENTS, AS DEFINED IN CHAPTER 381 FLORIDA
 STATUTES, CHAPTER 500 FLORIDA STATUTES AND CHAPTER 509
 FLORIDA STATUTES, SHALL COMPLY WITH THE APPLICABLE CODE
 REQUIREMENTS FOUND IN THE FLORIDA BUILDING CODE,
 BUILDING, CHAPTER 4, SPECIAL DETAILED REQUIREMENTS
 BASED ON USE AND OCCUPANCY. PLEASE SEE DBPR WEBSITE FOR
 ADDITIONAL INFO:
 HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/LICENSING/
 PLANREVIEWINDEX.HTML
  
 2) 2ND REVIEW THE REQUEST FOR REVIEW UNDER 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 2010 EDITION
 104.11 ALTERNATE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION IS BEING REVIEWED BY THE BUILDING OFFICIAL
 AND DIRECT WRITTEN RESPONCE FROM HIM.
 PLEASE NOTE GREASE INTERCEPTORS REQUIRE A SEPERATE
 PERMIT FOR RECORD RETENTION AND ENFORCEMENT OF THE
 CITIES FOG PROGRAM TO KEEP FROM HARMING THE CITIES
 SANITARY SYSTEM. PLEASE PROVIDE THE SIZE OF THE GREASE
 INTERCEPTOR, LOCATION AND PROVIDE THE CALCULATION FOR
 SIZING OF THE GREASE INTERCEPTOR.
 GREASE INTERCEPTORS THAT ARE SIZED, CONSTRUCTED AND
 APPROVED IN ACCORDANCE WITH RULE 64E-6, FLORIDA
 ADMINISTRATIVE CODE AND THAT ARE LOCATED OUTSIDE THE
 BUILDING SHALL USE THE FORUMULA FOUND IN FBC-P TABLE
 1003.5.1 FOR RESTARAUNTS. THIS CAN BE SUBMITTED UNDER
 THIS REVIEW, NOTED FOR A TURN AROUND PERMIT WHEN
 APPLIED FOR.
  
 3) 2ND REQUEST. THE GAS REVIEW IS CURRENTLY BEING
 COMPLETED UNDER THE PLUMBING PLAN REVIEW. IF THIS WAS
 THE ONLY ISSUE WITH THE PLUMBING PLAN REVIEW IT WOULD
 BE PULLED OUT AND TO THE SEPERATE FUEL GAS REVIEW.
 THESE COMMENTS WILL REAPPEAR UNDER THE HEADING OF THE
 GAS REVIEW. SEPARQATE PERMIT FOR GAS IS REQUIRED
 BECAUSE OF THE INSPECTION CODES ARE NOT PART OF A
 PLUMBING PERMIT,
  
 3A) SHEET P3.2 DETAIL 1A A OVERALL GAS RISER DIAGRAM
 INDICATES THE DESIGN TO BE NATURAL GAS, < THAN A 2 LB
 SYSTEM (1/2 LB) WITH A TOTAL OVER DISTANCE OF 125 FEET
 AND A PRESSURE DROP OF 0.3 IN W.C. AND SPECIFIC GRAVITY
 OF 0.60.
  
 3A)(1) WHEN READING THE LENGTH OF 125 FEET FOR 3 INCH
 BLACK PIPE THE TABLES INDICATE 2,190 CFH WHERE AS THE
 PLANS TOTAL LOAD IS 2,257 CFH WHICH IS LOW.
  
 3A)(2) THE SAME DETAIL P3.2 DETAIL 1A SHOWS A 3 INCH
 BRANCH OFF TO THE RTU UNITS ON THE ROOF. WHERE THIS T
 OCCURS THE PLANS INDICATE THE SIZE OF THE BLACK STEEL
 PIPE TO BE REDUCED TO 2 INCH (817 CFH, 125'). PLEASE
 REVIEW TABLE 402.4(1) FOR 125 FT, IT IS ONLY GOOD FOR
 777 CFH ON A 1/2 LB SYSTEM
  
 3A)(3) PLEASE PROVIDE A DETAIL FOR WHERE THE GAS LEAVES
 THE METER, IT APPEARS TO BE A MANIFOLD WITH A 3 INCH
 AND A 1 1/4 INCH PIPES LEAVING THE MANIFOLD. PLEASE
 PROVIDE WHAT SIZE PIPING THE MANIFOLD WILL BE CREATED
 FROM. ADDITIONAL INFORMATION IS REQUIRED.107.2.1.3.
  
 3A)(4) SHEET P3.2 DETAIL 1A NOTES INCLOSED BY A BOX
 INDICATE THE PIPE TO BE BLACK STEEL PIPE AND THE TABLE
 402.4(1) ALSO CONFIRMS SCHEDULE 40 METALLIC PIPE.
 SHEET P3.1 DETAIL GAS DETAIL AT COOK LINE INDICATES AS
 AN ALTERNATE TO WELDED FITTINGS TRACPIPE BY OMEGAFLEX
 MAY BE USED. TWO ISSUES WITH THIS.
 A) 2010 FBC-FUEL GAS 404.3 DOES NOT ALLOW FOR FITTINGS
 OR UNIONS WITH IN WALLS. STEEL PIPE WOULD BE ALLOWED
 WITH WELDS BUT THE TERM ALTERNATE IS NOT ALLWED.
 B) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL"
 OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 4) PLEASE PROVIDE COMPLIANCE WITH: 411.1.1 COMMERCIAL
 COOKING APPLIANCES.
 COMMERCIAL COOKING APPLIANCES INSTALLED ON CASTERS AND
 APPLIANCES THAT ARE MOVED FOR CLEANING AND SANITATION
 PURPOSES SHALL BE CONNECTED TO THE PIPING SYSTEM WITH
 AN APPLIANCE CONNECTOR LISTED AS COMPLYING WITH ANSI
 Z21.69 OR IN ACCORDANCE WITH ITEM 1 OR 3 OF SECTION
 411.1.
  
 411.1.2 PROTECTION AGAINST DAMAGE.
 CONNECTORS AND TUBING SHALL BE INSTALLED SO AS TO BE
 PROTECTED AGAINST PHYSICAL DAMAGE.
  
 411.1.3 CONNECTOR INSTALLATION.
 APPLIANCE FUEL CONNECTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS AND
 SECTIONS 411.1.3.1 THROUGH 411.1.3.4.
  
 411.1.3.1 MAXIMUM LENGTH.
 CONNECTORS SHALL HAVE AN OVERALL LENGTH NOT TO EXCEED 6
 FEET (1829 MM). MEASUREMENT SHALL BE MADE ALONG THE
 CENTERLINE OF THE CONNECTOR. ONLY ONE CONNECTOR SHALL
 BE USED FOR EACH APPLIANCE
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715