2014-04-12 18:07:19BUILDING PLAN REVIEW
 PERMIT: 14011102
 ADD: 1715 PALM BEACH LAKES
 RED ROBIN GOURMET BURGERS & BREWS
 CONTRACTOR: TO BE DETERMINED
 CONTACT: A & J
 TEL: (561) 373-3902 KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 RED ROBIN/ WEST PALM BEACH OUTLET MALL
 2ND REVIEW
 DATE: SAT. APRIL 12/2014
 ACTION: DENIED
  
 1-6) COMPLIED>
  
 7) SEMI-COMPLIED. SHEET S8.0 DOES PROVIDE THE WIND
 DESIGN CRITERIA IN VULT & VASD AS REQUESTEDAND WITH A C
 EXPOSURE THE WIND DESIGN DOES NOT PROVIDE THE MEAN ROOF
 HEIGHT AND THE ADJUSTMENT FACTOR FOR THE C EXPOSURE SEE
 2010 FBC-B TABLE 1609.7(2).
  
 1ST REVIEW COMMENT.. SHEET S8.0 IDENTIFIES THE BASE
 CODE 2009 IBC AS THE REFERENCED CODE, PLEASE CORRECT TO
 THE 2010 FBC-B THE WIND DESIGN CRITERIA IS CORRECT,
 PLEASE PROVIDE WIND PRESSURES FOR COMPONENTS AND
 CLADDING AT 10 SQ FT, 20 SQ FT AS WELL AS THE 50 SQ FT
 IN BOTH VULT AND VASD. FLORIDAS PRODUCT APPROVALS ARE
 IN VASD. PLEASE NOTE WE USE 10 SQ FT AS THE WORST CASE
 FOR ROOF FASTENERS.
  
 8) 2ND REQUEST, FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
  
 NOTE ONLY ONE SET OF PRODUCT APPROVALS WERE SUBMITTED.
  
 (31)(A) EXTERIOR DOORS, ROOF HATCHES.
 SHEET A2.1 UNDER THE HEADING OF GENERAL NOTES LIST THE
 EXTERIOR DOORS BY MANUFACTURER AND PRODUCT APPROVAL
 NUMBER
 11-0228.04 KAWNEER 350 IR STOREFRONT DOORS DOOR AND
 FRAME MAX. 98 1/2 INCHES IN HEIGHT. PLANS THE ENERGY
 CALCS INDICATE A SHGC OF 0.4 PROVIDE DOCUMENTATION.
  
 EXTERIOR DOORS HE HARDWARE SCHEDULE INDICATED THE USE
 OF A CONTINIOUS HINGE ON DOORS WHERE AS THE PRODUCT
 APPROVALS DO NOT INDICATE A CONTINIOUS HINGE.
  
 SUBMITTED CECO DOORS NOA 09-0505.09 THIS PRODUCT IS NOT
 LISTED ON SHEET A2.1, THE HOLLOW CORE METAL DOOR THAT
 IS LISTED IS A NOA 09-0323.23 WHICH IS A DIFFERNT
 MANUFACTURER, BUT IT IS ALSO A EXPIRED REPORT.
  
 REPORTS SUBMITTED BUT LISTED ON SHEET A2.1 ARE AS
 FOLLOWS:
 KAWNEER 11-1027.15 350 IR
 FL 5851-R3 YKK AP
  
 NO ROOF HATCH PRODUCT APPROVALS WERE SUBMITTED, IS
 LOCATED IN A ROOF ZONE 2 WITHIN 10'-0" OF THE EDGE OF
 THE ROOF.
  
 (B) WINDOWS
 SUBMITTED NOA 11-0915.06 KAWNEER IR-501 SERIES LMI
 PLEASE NOTE OVERALL HEIGHT LIMITATION OF 120 INCHES
 WHEREAS A2.1 WINDOW TYPE B SHOWS A OVERALL HEIGHT OF
 11'-10". PLEASE PROVIDE ADDITIONAL INFORMATION SHEET 3
 OF 9 INDICATES THE TYPE OF FASTENERS TO BE USED IN WOOD
 OR METAL STUDS. THE DETAIL SHOWS 4 1/2 INCH STRUCTURAL
 MEMBER THAT IS NOT SHOWN ON ANY A NOR S DRAWINGS,
 PLEASE PROVIDE WHAT TYPE OF STRUCTURAL SUPPORT THIS IS
 AND HOW IT WILL BE PART OF THE MWFRS.
 PLEASE ALSO PROVIDE DOCUMENTATION FOR THE SHGC OF 0.4.
  
 (C) EFISWALL SYSTEMS, PLEASE PROVIDE THE MANUFACTURERS
 INSTALATION BOOKLET. 2010 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 2010 EDITION 107.2.4 EXTERIOR WALL ENVELOPE.
 CONSTRUCTION DOCUMENTS FOR ALL BUILDINGS SHALL DESCRIBE
 THE EXTERIOR WALL ENVELOPE IN SUFFICIENT DETAIL TO
 DETERMINE COMPLIANCE WITH THIS CODE. THE CONSTRUCTION
 DOCUMENTS SHALL PROVIDE DETAILS OF THE EXTERIOR WALL
 ENVELOPE AS REQUIRED, INCLUDING FLASHING, INTERSECTIONS
 WITH DISSIMILAR MATERIALS, CORNERS, END DETAILS,
 CONTROL JOINTS, INTERSECTIONS AT ROOF, EAVES OR
 PARAPETS, MEANS OF DRAINAGE, WATER-RESISTIVE MEMBRANE
 AND DETAILS AROUND OPENINGS. THE CONSTRUCTION DOCUMENTS
 SHALL INCLUDE MANUFACTURER?S INSTALLATION INSTRUCTIONS
 THAT PROVIDE SUPPORTING DOCUMENTATION THAT THE PROPOSED
 PENETRATION AND OPENING DETAILS DESCRIBED IN THE
 CONSTRUCTION DOCUMENTS MAINTAIN THE WEATHER RESISTANCE
 OF THE EXTERIOR WALL ENVELOPE. THE SUPPORTING
 DOCUMENTATION SHALL FULLY DESCRIBE THE EXTERIOR WALL
 SYSTEM WHICH WAS TESTED, WHERE APPLICABLE, AS WELL AS
 THE TEST PROCEDURE USED.
  
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOFING
 INSULATION, ROOF CURBING
 DURO-LAST NOA 12-0529.09 WAS SUBMITTED BUT NO
 SUB-SYSTEM WAS IDENTIFIED WITH THE ASSOCIATED
 PRESSURES. MAY REQUIRE ENHANCED FASTENING SEE
 LIMITATION #7 VERSES #9. 107.2.1.2 FOR ROOF ASSEMBLIES
 REQUIRED BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL
 ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING
 SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT
 BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST
 BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS.
  
 NO PRODUCT APPROVALS WERE SUBMITTED FOR ROOF TOP CURBS.
  
 (G) PRE-ENGINEERED A/C STANDS SHEET A2.3 DOES SHOW ROOF
 TOP CONDENSING UNITS THAT WILL REQUIRE ROOF TOP STANDS,
 THESE STANDS WILL ALSO NEED TO CONSIDER THE AMOUNT OF
 ROOF TOP INSULATION THAT WILL BE REQUIRED BY THE ENERGY
 CODE SO THEY WILL STILL COMPLY WITH FBC-B TABLE 1509.7
 CLEARANCE BENEATH THE STAND TO THE FINISH ROOF TOP.
  
 9) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10-11) COMPLIED.
  
 12) 2ND REQUEST SEMI-COMPLIED. 1408.5 INSTALLATION.
 INSTALLATION OF THE EIFS AND EIFS WITH DRAINAGE SHALL
 BE IN ACCORDANCE WITH THE EIFS MANUFACTURER?S
 INSTRUCTIONS.
  
 13) 2ND REQUEST. PLEASE REVIEW THE DRYVIT NOA
 11-1108.01 AND THEIR INSTALATION INSTRUCTIONS FOR THE
 REQUIEMENTS FOR SILL FLASHING DETAILS AND REQUIREMENTS,
 PLEASE PROVIDE THE TYPE OF MATERIAL AND MINIMUM
 THICKNESS OF THE SILL FLASHING, AND TYPE OF SEALANTS TO
 BE USED IN THE INSTALATION.
 PROVIDE FLASHING DETAILS FOR WINDOWS AND DOORS, 2010
 FBC-B 1405.4. FLASHING SHALL BE INSTALLED IN SUCH A
 MANNER SO AS TO PREVENT MOISTURE FROM ENTERING THE WALL
 OR TO REDIRECT IT TO THE EXTERIOR. FLASHING SHALL BE
 INSTALLED AT THE PERIMETERS OF EXTERIOR DOOR AND WINDOW
 ASSEMBLIES, PENETRATIONS AND TERMINATIONS OF EXTERIOR
 WALL ASSEMBLIES, EXTERIOR WALL INTERSECTIONS WITH
 ROOFS, CHIMNEYS, PORCHES, DECKS, BALCONIES AND SIMILAR
 PROJECTIONS AND AT BUILT-IN GUTTERS AND SIMILAR
 LOCATIONS WHERE MOISTURE COULD ENTER THE WALL.
  
 14 )2ND REQUEST. THE TRUSS MANUFACTURER ONY DESIGNS THE
 TRUSS TO TRUSS CONNECTIONS. THE STRUCTURAL ENGINEEER
 PROVIDES A OVER ALL LAYOUT AND THE LOADS TO BE RESISTED
 FOR EACH TRUSS. SHEET S2.0 PROVIDES A LAYOUT OF THE
 TRUSSES AND GIRDERS, THE PLANS DOES NOT SHOW HOW THE
 UPLIFT LOADS ARE GOING TO BE TRANSFERRED INTO THE WALLS
 AND MWFRS. PROVIDE LOADS TO BE REISTED, PLEASE ALSO
 PROVIDE WHAT ADDITIONAL TRUSS HARDWARE BEARING CLIPS
 ETC FOR THE RED S BUILT TRUSS SYSTEM.
  
 FL ADMINISTRATIVE CODE. 61G15-31.003 DESIGN OF
 STRUCTURES UTILIZING PREFABRICATED WOOD TRUSSES.
 (1) WHEN A STRUCTURAL ENGINEER OF RECORD AND A
 DELEGATED ENGINEER EXIST AS MAY BE DETERMINED BY
 APPLICABLE FLORIDA LAW, THE APPORTIONMENT OF
 RESPONSIBILITIES BETWEEN THE STRUCTURAL ENGINEER OF
 RECORD AND A DELEGATED ENGINEER SHALL BE AS SET FORTH
 IN CHAPTER 2 OF ANSI/TPI 1-1995, WHEREIN THE STRUCTURAL
 ENGINEER OF RECORD IS THE BUILDING DESIGNER AND THE
 DELEGATED ENGINEER IS THE TRUSS DESIGNER AS THOSE TERMS
 ARE DEFINED IN SAID STANDARD.
 (2) THE STRUCTURAL ENGINEER OF RECORD SHALL PROVIDE
 DESIGN REQUIREMENTS IN WRITING TO THE DELEGATED
 ENGINEER AND SHALL REVIEW THE DESIGN DOCUMENTS OF THE
 DELEGATED ENGINEER FOR CONFORMANCE TO HIS WRITTEN
 INSTRUCTIONS IN ACCORDANCE WITH RULE 61G15-30.005,
 F.A.C.
  
  
 15) COMPLIED.
  
  
 NEW COMMENTS
  
 16) SHEET A1.1 DETAIL # 15 REVISION # 2 USES THE TERM
 OR IN REGARDS TO SIMPSON A21 OR METAL BRACKETS. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH DRAWINGS
 AND SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE
 FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 17) THE STRUCTURAL SHEETS S1.0, S3.0, S4.0, S5.0 & S8.0
 ARE ALL PHOTO-COPIED SIGNATURES NOT ORIGINALS. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009
  
 18) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER