2014-02-22 16:49:22PLUMBING PLAN REVIEW
 PERMIT: 14011102
 ADD: 1715 PALM BEACH LAKES
 RED ROBIN GOURMET BURGERS & BREWS
 CONTRACTOR: TO BE DETERMINED
 CONTACT: A & J
 TEL: (561) 373-3902 KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED
 APRIL 25/2013.
  
 1ST REVIEW
 DATE: SAT. FEB. 22/2014
 ACTION: DENIED
  
 1) 2010 FBC-PLUMB.315.1 REQUIREMENTS. PUBLIC FOOD
 SERVICE ESTABLISHMENTS AND FOOD ESTABLISHMENTS, AS
 DEFINED IN CHAPTER 381 FLORIDA STATUTES, CHAPTER 500
 FLORIDA STATUTES AND CHAPTER 509 FLORIDA STATUTES,
 SHALL COMPLY WITH THE APPLICABLE CODE REQUIREMENTS
 FOUND IN THE FLORIDA BUILDING CODE, BUILDING, CHAPTER
 4, SPECIAL DETAILED REQUIREMENTS BASED ON USE AND
 OCCUPANCY. PLEASE SEE DBPR WEBSITE FOR ADDITIONAL INFO:
 HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/LICENSING/
 PLANREVIEWINDEX.HTML
  
 2) PLEASE NOTE GREASE INTERCEPTORS REQUIRE A SEPERATE
 PERMIT FOR RECORD RETENTION AND ENFORCEMENT OF THE
 CITIES FOG PROGRAM TO KEEP FROM HARMING THE CITIES
 SANITARY SYSTEM. PLEASE PROVIDE THE SIZE OF THE GREASE
 INTERCEPTOR, LOCATION AND PROVIDE THE CALCULATION FOR
 SIZING OF THE GREASE INTERCEPTOR.
 GREASE INTERCEPTORS THAT ARE SIZED, CONSTRUCTED AND
 APPROVED IN ACCORDANCE WITH RULE 64E-6, FLORIDA
 ADMINISTRATIVE CODE AND THAT ARE LOCATED OUTSIDE THE
 BUILDING SHALL USE THE FORUMULA FOUND IN FBC-P TABLE
 1003.5.1 FOR RESTARAUNTS. THIS CAN BE SUBMITTED UNDER
 THIS REVIEW, NOTED FOR A TURN AROUND PERMIT WHEN
 APPLIED FOR.
  
 3) THE SHEET P3.2 DOES HAVE A GAS RISER PLAN BUT NOT
 ENOUGH INFORMATION IS PROVIDED TO BE ABLE TO COMPLETE A
 GAS REVIEW AT THIS TIME, A LIST OF REQUIREMENTS IS
 LISTED BELOW.
 3.1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 3.2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. FUEL GAS
 402.3.
  
 3.3. TYPE OF GAS, (LP OR NATURAL).
  
 3.4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS.
 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 3.5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 3.6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 3.7 INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 3.8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS
 CODE SEC. 502 THRU 505.
  
 3.9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 4) SHEET A 2.3 THE ROOF PLAN PLEASE SIZE ROOF FOR
 DRAINAGE, INCLUDE 1/2 THE HEIGTH OF THE PARAPET WALLS,
 RAINFALL CHART FIGURE 1106.1 INDICATES PALM BEACH
 COUNTY AS 4.5 INCHES 100 YEAR ONE HOUR RAIN FALL :
  
 4A) SHEET A 2.3 INDICATES THE BACK HALF OF THE ROOF TO
 BE DRAINED WITH THROUGH THE WALL SCUPPERS AND EMERGENCY
 OVER FLOW THIS SAME SHEET INDICATES DETAILS 24 & 25 /
 A4.2 THESE DETAILS CAN NOT BE FOUND. PLEASE SIZE
 SCUPPERS AND OVERFLOWS TO TABLE FBC-P 1106.7.
  
 4B) THE FRONT HALF OF THE ROOF IS SLOPED TO GUTTER,
 DETAIL 4 OF A4.2 INDICATES THE GUTTER, BUT THE
 ANCHORING OF THE GUTTER SYSTEM IS LACKING, NEITHER IS
 THERE
 SIZING OF THE GUTTER FOR THE 100 YEARRAIN FOR ONE HOUR
 AT 4.5 INCHES NOR FOR THE VERTICAL CONDUCTORS OR
 LEADERS, THE PLAN IS NOT CLEAR IF THEY ARE TO RUN
 INSIDE OF THE BUILDING OR ON THE EXTERIOR. SEE TABLES
 1106.2 FOR VERTICAL & 1106.3 FOR HORIZONTAL PIPING.
  
 4C) 2010 FBC-P 1107.1 REQUIRES A SECONDARY DRAINAGE
 SYSTEM, WHAT PROVISIONS ARE BEING MADE FOR THE GUTTER
 SYSTEM, IF THIS IS PLUGGED OR OVER FLOWS THE WATERS
 WILL TRAVEL DOWN THE LOWER ROOF TO THE SCUPPERS AND
 OVER FLOW SCUPPERS, PROVIDE ADDITIONAL INFORMATION, ARE
 TO BE OVERSIZED FOR THIS TYPE OF SITUATION?
  
 4D) PROVIDE HOW THE RAIN WATER RUN OFF WILL BE DRAINED
 AWAY FROM THE BUILDING, CIVIL SHOWED THE TIE INTO THE
 STORM DRAIN, WHAT WILL KEEP THE RAINWATER FROM BACKING
 UP AND ONTO THE ROOF IF THE STORM SYSTEM IS BLOCKED OR
 FULL? PROVISIONS FOR OVERFLOW?
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO