Text |
| 2014-02-22 16:49:22 | PLUMBING PLAN REVIEW |
| | PERMIT: 14011102 |
| | ADD: 1715 PALM BEACH LAKES |
| | RED ROBIN GOURMET BURGERS & BREWS |
| | CONTRACTOR: TO BE DETERMINED |
| | CONTACT: A & J |
| | TEL: (561) 373-3902 KARI |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED |
| | APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. FEB. 22/2014 |
| | ACTION: DENIED |
| | |
| | 1) 2010 FBC-PLUMB.315.1 REQUIREMENTS. PUBLIC FOOD |
| | SERVICE ESTABLISHMENTS AND FOOD ESTABLISHMENTS, AS |
| | DEFINED IN CHAPTER 381 FLORIDA STATUTES, CHAPTER 500 |
| | FLORIDA STATUTES AND CHAPTER 509 FLORIDA STATUTES, |
| | SHALL COMPLY WITH THE APPLICABLE CODE REQUIREMENTS |
| | FOUND IN THE FLORIDA BUILDING CODE, BUILDING, CHAPTER |
| | 4, SPECIAL DETAILED REQUIREMENTS BASED ON USE AND |
| | OCCUPANCY. PLEASE SEE DBPR WEBSITE FOR ADDITIONAL INFO: |
| | HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/LICENSING/ |
| | PLANREVIEWINDEX.HTML |
| | |
| | 2) PLEASE NOTE GREASE INTERCEPTORS REQUIRE A SEPERATE |
| | PERMIT FOR RECORD RETENTION AND ENFORCEMENT OF THE |
| | CITIES FOG PROGRAM TO KEEP FROM HARMING THE CITIES |
| | SANITARY SYSTEM. PLEASE PROVIDE THE SIZE OF THE GREASE |
| | INTERCEPTOR, LOCATION AND PROVIDE THE CALCULATION FOR |
| | SIZING OF THE GREASE INTERCEPTOR. |
| | GREASE INTERCEPTORS THAT ARE SIZED, CONSTRUCTED AND |
| | APPROVED IN ACCORDANCE WITH RULE 64E-6, FLORIDA |
| | ADMINISTRATIVE CODE AND THAT ARE LOCATED OUTSIDE THE |
| | BUILDING SHALL USE THE FORUMULA FOUND IN FBC-P TABLE |
| | 1003.5.1 FOR RESTARAUNTS. THIS CAN BE SUBMITTED UNDER |
| | THIS REVIEW, NOTED FOR A TURN AROUND PERMIT WHEN |
| | APPLIED FOR. |
| | |
| | 3) THE SHEET P3.2 DOES HAVE A GAS RISER PLAN BUT NOT |
| | ENOUGH INFORMATION IS PROVIDED TO BE ABLE TO COMPLETE A |
| | GAS REVIEW AT THIS TIME, A LIST OF REQUIREMENTS IS |
| | LISTED BELOW. |
| | 3.1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| | FBC-2010 FUEL GAS. |
| | |
| | 3.2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS |
| | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. FUEL GAS |
| | 402.3. |
| | |
| | 3.3. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | 3.4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD |
| | ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. |
| | 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) |
| | |
| | 3.5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? |
| | USE OF CAPACITY SECTION A.3.1(4) |
| | |
| | 3.6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2010 FUEL GAS CODE SEC. 304 |
| | |
| | 3.7 INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 |
| | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| | PSI. |
| | |
| | 3.8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| | AND TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS |
| | CODE SEC. 502 THRU 505. |
| | |
| | 3.9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2010 FUEL GAS SEC. 402.2 |
| | |
| | 4) SHEET A 2.3 THE ROOF PLAN PLEASE SIZE ROOF FOR |
| | DRAINAGE, INCLUDE 1/2 THE HEIGTH OF THE PARAPET WALLS, |
| | RAINFALL CHART FIGURE 1106.1 INDICATES PALM BEACH |
| | COUNTY AS 4.5 INCHES 100 YEAR ONE HOUR RAIN FALL : |
| | |
| | 4A) SHEET A 2.3 INDICATES THE BACK HALF OF THE ROOF TO |
| | BE DRAINED WITH THROUGH THE WALL SCUPPERS AND EMERGENCY |
| | OVER FLOW THIS SAME SHEET INDICATES DETAILS 24 & 25 / |
| | A4.2 THESE DETAILS CAN NOT BE FOUND. PLEASE SIZE |
| | SCUPPERS AND OVERFLOWS TO TABLE FBC-P 1106.7. |
| | |
| | 4B) THE FRONT HALF OF THE ROOF IS SLOPED TO GUTTER, |
| | DETAIL 4 OF A4.2 INDICATES THE GUTTER, BUT THE |
| | ANCHORING OF THE GUTTER SYSTEM IS LACKING, NEITHER IS |
| | THERE |
| | SIZING OF THE GUTTER FOR THE 100 YEARRAIN FOR ONE HOUR |
| | AT 4.5 INCHES NOR FOR THE VERTICAL CONDUCTORS OR |
| | LEADERS, THE PLAN IS NOT CLEAR IF THEY ARE TO RUN |
| | INSIDE OF THE BUILDING OR ON THE EXTERIOR. SEE TABLES |
| | 1106.2 FOR VERTICAL & 1106.3 FOR HORIZONTAL PIPING. |
| | |
| | 4C) 2010 FBC-P 1107.1 REQUIRES A SECONDARY DRAINAGE |
| | SYSTEM, WHAT PROVISIONS ARE BEING MADE FOR THE GUTTER |
| | SYSTEM, IF THIS IS PLUGGED OR OVER FLOWS THE WATERS |
| | WILL TRAVEL DOWN THE LOWER ROOF TO THE SCUPPERS AND |
| | OVER FLOW SCUPPERS, PROVIDE ADDITIONAL INFORMATION, ARE |
| | TO BE OVERSIZED FOR THIS TYPE OF SITUATION? |
| | |
| | 4D) PROVIDE HOW THE RAIN WATER RUN OFF WILL BE DRAINED |
| | AWAY FROM THE BUILDING, CIVIL SHOWED THE TIE INTO THE |
| | STORM DRAIN, WHAT WILL KEEP THE RAINWATER FROM BACKING |
| | UP AND ONTO THE ROOF IF THE STORM SYSTEM IS BLOCKED OR |
| | FULL? PROVISIONS FOR OVERFLOW? |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |