| Plan Review Notes For Permit 14011102 |
| Permit Number |
14011102 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-18 12:12:50 | 14011102 | | | 1715 PALM BEACH LAKES | | | RED ROBIN GOURMET BURGERS AND BREWS | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | FEEDERS TO THE MDP ARE UNDERSIZED. THE PLAN INDICATES | | | THE MAIN DISCONNECT IS 1000 AMPERES. NEC 310.16, 240.6, | | | 240.4(C) | | | PANEL LA, AND PANEL M REQUIRE LARGER FEEDERS. NEC 240.4 | | | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 | | | | | | PROVIDE VOLTAGE DROP CALCULATION VERIFYING COMPLIANCE | | | WITH THE ENERGY CODE. FBC-EC 505.7.3 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING | | | MEANS. NEC 110.22, 110.16, 110.22 | | | | | | PROVIDE DIMENSIONS FOR THE DESIGNATED CLEAR WORKING | | | SPACES REQUIRED AROUND THE ELECTRICAL SERVICE EQUIPMENT | | | AND PANEL BOARDS. NEC 215.5, 110.26 | | | | | | WIRING METHODS FOR DATA WHICH ARE LOCATED BELOW GRADE | | | MUST BE LISTED FOR WET LOCATIONS. NEC 110.11 | | | | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR SITE | | | LIGHTING, ALARM, SECURITY AND DATA SYSTEMS. | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | | | | | | | |
|