Plan Review Notes
Plan Review Notes For Permit 14011102
Permit Number 14011102
Review Stop B
Sequence Number 1
Notes
Date Text
2014-02-22 16:48:27BUILDING PLAN REVIEW
 PERMIT: 14011102
 ADD: 1715 PALM BEACH LAKES
 RED ROBIN GOURMET BURGERS & BREWS
 CONTRACTOR: TO BE DETERMINED
 CONTACT: A & J
 TEL: (561) 373-3902 KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. FEB. 22/2014
 ACTION: DENIED
  
 1) THE COVER SHEET CS1.0 INDICATES THIS BUILDING WAS
 DESIGNED UNDER THE 2007 FBC, PLEASE BE AWARE FLORIDA
 ADOPTED THE 2010 FLORIDA FAMILY OF CODES STATEWIDE
 MARCH 15, 2012. PLEASE UPDATE PLANS ACCORDINGLY.
  
 2) PLEASE PROVIDE ORIGINAL SOILS REPORTS 2010 FBC-B
 803.2 INVESTIGATIONS REQUIRED. GEOTECHNICAL
 INVESTIGATIONS SHALL BE CONDUCTED IN ACCORDANCE WITH
 SECTIONS 1803.3 THROUGH 1803.5.
  
 3) THIS BUILDING IS CLASSIFIED AS A LL-B BUILDING,
 PLEASE CONTACT THE MANAGER OF RESIDENT INSPECTORS TO
 SEE IF A RESIDENT INSPECTOR WILL BE REQUIRED FOR THIS
 BUILDING. 110.3.9 OTHER INSPECTIONS SERVICES. THE
 BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY
 OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. HE/SHE
 MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED
 INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION
 HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND
 RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION
 OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH
 REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY
 A RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES: 1. FOR BUILDINGS OR
 ADDITIONS OF TYPE I OR II CONSTRUCTION.
 MANAGER OF THRESHOLD & RESIDENT INSPECTOR PROGRAM
 KEN CONRAD
 TEL 561-805-6666
 E-MAIL: [email protected]
  
 4) THIS BUILDING BEING CLASSIFIED AS A BUILDING TYPE
 LL-B CONSTRUCTION WILL REQUIRE ALL FRAMING, SHEATHING
 AND OR DECKING TO BE FIRE RETARDANT TREATED WOOD.
 2010 FBC-B 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS
 REQUIRED.
 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING.
  
 5) 2304.9.5.4 FASTENERS FOR FIRE-RETARDANT-TREATED WOOD
 USED IN INTERIOR APPLICATIONS.
 FASTENERS FOR FIRE-RETARDANT-TREATED WOOD USED IN
 INTERIOR LOCATIONS SHALL BE IN ACCORDANCE WITH THE
 MANUFACTURER?S RECOMMENDATIONS. IN THE ABSENCE OF
 MANUFACTURER?S RECOMMENDATIONS, SECTION 2304.9.5.3
 SHALL APPLY.
  
 6) SHEET S3.0 PROVIDES DETAILS FOR STEM WALL
 CONSTRUCTION AND NOTES FOR VAPOR BARRIER BENEATH THE
 SLAB BUT THERE IS NO MENTION OF HOW TERMITE PROTECTION
 WILL BE ACHIEVED, SEE 2010 FBC-B 1816.1.
  
 7) SHEET S8.0 IDENTIFIES THE BASE CODE 2009 IBC AS THE
 REFERENCED CODE, PLEASE CORRECT TO THE 2010 FBC-B THE
 WIND DESIGN CRITERIA IS CORRECT, PLEASE PROVIDE WIND
 PRESSURES FOR COMPONENTS AND CLADDING AT 10 SQ FT, 20
 SQ FT AS WELL AS THE 50 SQ FT IN BOTH VULT AND VASD.
 FLORIDAS PRODUCT APPROVALS ARE IN VASD. PLEASE NOTE WE
 USE 10 SQ FT AS THE WORST CASE FOR ROOF FASTENERS.
  
 8) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, ROOF HATCHES.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFISWALL SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOFING
 INSULATION, ROOF CURBING
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 9) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) SHEET A4.1 INDICATES THE USE OF STONE VENEER ON
 METAL LATH OVER A WATER RESISTANT BARRIER. PLEASE SHOW
 COMPLIANCE WITH:
 FBC-B 1404.2.1
 WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED TO LATH
 OVER FRAME CONSTRUCTION, MEASURES SHALL BE TAKEN TO
 PREVENT BONDING BETWEEN THE CEMENT PLASTER AND THE
 WATER RESISTIVE BARRIER. A BOND BREAK SHALL BE PROVIDED
 BETWEEN THE WATER RESISTIVE BARRIER AND THE CEMENT
 PLASTER (STUCCO) CONSISTING OF ONE OF THE FOLLOWING:
 1. TWO LAYERS OF AN APPROVED WATER RESISTANT BARRIER OR
 2. ONE LAYER OF AN APPROVED WATER RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP, OR
 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS.
  
 11) SHEET A4.1 DETAILS 3, 4 & 5 ALL SHOW THE USE OF
 EFIS AS A EXTERIOR FINISH 1406.2 COMBUSTIBLE EXTERIOR
 WALL COVERINGS.
 COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL COMPLY WITH
 THIS SECTION. EXCEPTION: PLASTICS COMPLYING WITH
 CHAPTER 26. PROVIDE DOCUMENTATION THAT THE EFIS PRODUCT
 WILL MEET THIS CODE REQUIREMENT. 2603.4.1.4 EXTERIOR
 WALLS?ONE-STORY BUILDINGS.
 FOR ONE-STORY BUILDINGS, FOAM PLASTIC HAVING A FLAME
 SPREAD INDEX OF 25 OR LESS, AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450, SHALL BE PERMITTED WITHOUT
 THERMAL BARRIERS IN OR ON EXTERIOR WALLS IN A THICKNESS
 NOT MORE THAN 4 INCHES (102 MM) WHERE THE FOAM PLASTIC
 IS COVERED BY A THICKNESS OF NOT LESS THAN
 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A BASE METAL THICKNESS
 OF 0.0160 INCH (0.41 MM) AND THE BUILDING IS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1.
  
 12) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1408.3
 STRUCTURAL DESIGN.
 THE UNDERLYING STRUCTURAL FRAMING AND SUBSTRATE SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST LOADS AS REQUIRED
 BY CHAPTER 16.
 1408.4 WEATHER RESISTANCE.
 EIFS SHALL COMPLY WITH SECTION 1403 AND SHALL BE
 DESIGNED AND CONSTRUCTED TO RESIST WIND AND RAIN IN
 ACCORDANCE WITH THIS SECTION AND THE MANUFACTURER?S
 APPLICATION INSTRUCTIONS.
 1408.4.1 EIFS WITH DRAINAGE.
 EIFS WITH DRAINAGE SHALL HAVE AN AVERAGE MINIMUM
 DRAINAGE EFFICIENCY OF 90 PERCENT WHEN TESTED IN
 ACCORDANCE THE REQUIREMENTS OF ASTM E 2273 AND IS
 REQUIRED ON FRAMED WALLS OF TYPE V CONSTRUCTION, GROUP
 R1, R2, R3 AND R4 OCCUPANCIES.
 1408.4.1.1 WATER-RESISTIVE BARRIER.
 FOR EIFS WITH DRAINAGE, THE WATER-RESISTIVE BARRIER
 SHALL COMPLY WITH SECTION 1404.2 OR ASTM E 2570.
 1408.5 INSTALLATION.
 INSTALLATION OF THE EIFS AND EIFS WITH DRAINAGE SHALL
 BE IN ACCORDANCE WITH THE EIFS MANUFACTURER?S
 INSTRUCTIONS.
  
 13) PROVIDE FLASHING DETAILS FOR WINDOWS AND DOORS,
 2010 FBC-B 1405.4. FLASHING SHALL BE INSTALLED IN SUCH
 A MANNER SO AS TO PREVENT MOISTURE FROM ENTERING THE
 WALL OR TO REDIRECT IT TO THE EXTERIOR. FLASHING SHALL
 BE INSTALLED AT THE PERIMETERS OF EXTERIOR DOOR AND
 WINDOW ASSEMBLIES, PENETRATIONS AND TERMINATIONS OF
 EXTERIOR WALL ASSEMBLIES, EXTERIOR WALL INTERSECTIONS
 WITH ROOFS, CHIMNEYS, PORCHES, DECKS, BALCONIES AND
 SIMILAR PROJECTIONS AND AT BUILT-IN GUTTERS AND SIMILAR
 LOCATIONS WHERE MOISTURE COULD ENTER THE WALL.
  
 14) SHEET S2.0 PROVIDES A LAYOUT OF THE TRUSSES AND
 GIRDERS, THE PLANS DOES NOT SHOW HOW THE UPLIFT LOADS
 ARE GOING TO BE TRANSFERRED INTO THE WALLS AND MWFRS.
 PROVIDE LOADS TO BE REISTED, PLEASE ALSO PROVIDE WHAT
 ADDITIONAL TRUSS HARDWARE BEARING CLIPS ETC FOR THE RED
 S BUILT TRUSS SYSTEM.
  
 15) THIS BUILDING IS BEING DESIGNED AS A TYPE II-B
 BUILDING WHICH REQUIRES FIRE RETARANT WOOD WITHIN THE
 FRAMING MEMBERS AS WELL AS TRUSSES. WILL THE RED BUILT
 TRUSS SYSTEM COME AS A FIRE RETARDANT TREATED MATERIAL
 OR WOULD THE TREATMENT OCCUR IN THE FIELD? WILL THIS
 VOID THE WARRENTY.
  
 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]