| 2014-01-23 07:08:12 | BUILDING PLAN REVIEW |
| | |
| | REVISION: 14911087 |
| | PERMIT: 13070893 |
| | ADD: 511/513 S OLIVE |
| | CONT: MVP CONTRACTORS |
| | TEL: (954)214-0226 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURSDAY JAN. 23/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 2 IS SUBMITTED AS A ARCHITECTURAL CHANGE ONLY. |
| | IN THE ORIGINAL ISSUED PERMIT SET OF PLANS SHEET # 7 |
| | PLUMBING ISOMETRIC THE NOW SINK WAS CLASSIFIED AS A |
| | LAVATORY NOT A SINK. THE REVISION FOR THE SAME SHEET |
| | CITY DATE STAMP NOV. 25TH/ 2013 ALSO INDICATES THIS TO |
| | BE A LAVATORY. NOW THE ARCHITECTURAL SHEET SUBMITTED |
| | DATED 1/17/2014 RENAMES THE FIXTURE AS A SINK. WE WILL |
| | NEED A UPDATED PLUMBING SHEET FOR WASTE SHOWING THE |
| | ISOMETRIC FOR THE WASTE & VENT. |
| | |
| | NOTE SHEET 7 SHOWS THE RESTROOM DROUP AS WET VENTED, |
| | ONLY FIXTURES FOUND IN A BATHROOM GROUP CAN BE WET |
| | VENTED, NOT A SINK, THE SINK SHOULD TIE IN BELOW THE |
| | WET VENT SYSTEM. 2010 FBC-P 909.1 HORIZONTAL WET VENT |
| | PERMITTED. |
| | |
| | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS |
| | LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE |
| | VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE |
| | CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND |
| | FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION |
| | OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM |
| | FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH |
| | DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT |
| | INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE |
| | FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO |
| | THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL |
| | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL |
| | WET VENT. |
| | |
| | BOAF INFORMAL INTERPRETATION # 6090 WET VENT AND |
| | BATHROOM GROUPS. MON. APRIL 13, 2009 |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |