2014-03-28 11:43:552010 FBC
  
 DENIED
  
 1) THE TOTAL LOAD WITH THE 64,000 BTU BBQ IS NOW
 334,000 BTU. THE 1" METALLIC PIPE FROM THE METER TO THE
 FIRST BRANCH IS 320,000 BTU WITH A 40 FT LENGTH PER
 TABLE 402.4(2)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]