Date Text
2014-02-04 13:52:232010 FBC
  
 DENIED
  
 1) THE 1/2" CSST THAT IS SPECIFIED IS RATED FOR 47,000
 BTU. ACCORDING TO THE PLANS THE BBQ REQUIRES 48,000
 BTU. THE PLANS INCORRECTLY SPECIFY FBC TABLE 402.4 (15)
 . THE CORRECT ONE IS TABLE 402.4 (13). PLEASE REVISE
 THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]