1 |
|
| Notes |
| Date |
Text |
| 2014-02-04 13:52:23 | 2010 FBC | | | | | | DENIED | | | | | | 1) THE 1/2" CSST THAT IS SPECIFIED IS RATED FOR 47,000 | | | BTU. ACCORDING TO THE PLANS THE BBQ REQUIRES 48,000 | | | BTU. THE PLANS INCORRECTLY SPECIFY FBC TABLE 402.4 (15) | | | . THE CORRECT ONE IS TABLE 402.4 (13). PLEASE REVISE | | | THE PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|