| 2014-01-21 18:22:04 | FUEL GAS PLAN REVIEW |
| | PERMIT: 14010954 |
| | ADD: 608 ARDMORE RD |
| | CONT: TKO PLUMBING |
| | TEL: (561)827-9895 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JAN. 21/2014 |
| | ACTION: DENIED |
| | 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| | FBC-2010 RESIDENTIAL OR 2010 FUEL GAS CODE. |
| | |
| | 2) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| | THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS CODE SECS. |
| | 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(33) OR |
| | RESIDENTIAL CODE SECTIONS G2412.8 THRU G2413.6.1 AND |
| | TABLES G2413.4(1) THRU 2413.4(8). |
| | |
| | 3) FBC-2010 FUEL GAS SEC. 404.12 OUTLET CLOSURES: GAS |
| | OUTLETS THAT DO NOT CONNECT TO APPLIANCES SHALL BE |
| | CAPPED GAS |
| | TIGHT. |
| | |
| | 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER |
| | FBC-2010 FUEL GAS CODE APPENDIX A - USE OF CAPACITY |
| | TABLES A.3.1(4). |
| | |
| | 5) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 |
| | FUEL GAS CODE SEC. 402.2. NATURAL GAS SPECIFY .5 PSI OR |
| | 2 PSI. |
| | |
| | 6) SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | THE |
| | FBC-2010 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE |
| | SEC. G2413.2. |
| | |
| | 7) TANKLESS WATER HEATER, PROVIDE MANUFACTURERS |
| | SPECIFICATIONS FOR VENTING, EVEN FOR OUTDOOR UNITS |
| | SINCE THERE ARE CLEARENCES REQUIRED FROM WINDOW AND |
| | DOORS. 502 THRU 505 & G2426 THRU G2429. |
| | |
| | |