| Plan Review Notes For Permit 14010938 |
| Permit Number |
14010938 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-10 11:56:13 | THIS PERMIT IS BEING CONDITIONALLY APPROVED AS FOLLOWS: | | | 1. SHOW WINDOWS 2 & 3 ARE MISSING THE OUTLETS AS | | | REQUIRED BY NEC 210.62 | | | 2. THE SOUND SYSTEM SHALL BE AUTOMATICALLY MUTED BY THE | | | FIRE ALARM CONTROL PANEL IN THE EVENT OF AN ALARM | | | 3. ALL LOW VOLTAGE WIRING SHALL BE APPROVED AND LISTED | | | FOR THE APPLICATION. | | | | | | IT IS ASSUMED THAT ALL EMERGENCY LIGHTING IS AS | | | REQUIRED BY CODE. |
|