| 2014-02-05 06:42:37 | BUILDING PLAN REVIEW |
| | PERMIT: 14010912 |
| | ADD: 3613 BROADWAY |
| | CONT: THE BRIGHTSTONE GROUP |
| | TEL: (561)889-7206 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 05/2014 |
| | ACTION: DENIED |
| | |
| | 2010 FL EXISTING BUILDING CODE 901.3 CHANGE OF |
| | OCCUPANCY CLASSIFICATION. |
| | WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| | CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912 |
| | SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| | CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| | OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| | GROUP. THE COVERSHEET DOES NOT DISCLOSE IF THIS IS A |
| | FIRE SPRINKLERED BUILDING, UNDER THE 2010 FBC EXISTING |
| | BUILDING CODE SECTION 904.1 |
| | |
| | |
| | 1) GROUND FLOOR PLAN SHEET 01 INDICATES UNDER THE |
| | HEADING CHANGE OF USE FBC 2010 CHAPTER 3 SECTION 310 A |
| | R-3 OCCUPANCY. ONE & 2 FAMILY BUILDINGS ARE A R-3 |
| | OCCUPANCY, THIS IS CONSIDERED A R-2 OCCUPANCY, PLEASE |
| | CORRECT. |
| | |
| | 2) PLEASE LABEL HOW MANY UNITS WITHIN THIS STRUCTURE |
| | ARE HOW MANY ARE SLEEPING UNITS AND HOW MANY ARE |
| | DWELLING UNITS. PROVIDE THE SQUARE FOOTAGE FOR EACH |
| | UNIT. PROVIDE COMPLIANCE WITH : |
| | 2A) SEE DEFINITION OF : |
| | |
| | 2A)(1) DWELLING 1208.3 ROOM AREA. EVERY DWELLING UNIT |
| | SHALL HAVE AT LEAST ONE ROOM THAT SHALL HAVE NOT LESS |
| | THAN 120 SQUARE FEET (13.9 M2) OF NET FLOOR AREA. OTHER |
| | HABITABLE ROOMS SHALL HAVE A NET FLOOR AREA OF NOT LESS |
| | THAN 70 SQUARE FEET (6.5 M2). |
| | EXCEPTION: EVERY KITCHEN IN A ONE- AND TWO-FAMILY |
| | DWELLING SHALL HAVE NOT LESS THAN 50 SQUARE FEET (4.64 |
| | M2) OF GROSS FLOOR AREA. |
| | |
| | 2A)(2) EFFICIENCY DWELLING UNIT. 1208.4 EFFICIENCY |
| | DWELLING UNITS. AN EFFICIENCY LIVING UNIT SHALL CONFORM |
| | TO THE REQUIREMENTS OF THE CODE EXCEPT AS MODIFIED |
| | HEREIN: |
| | 1. THE UNIT SHALL HAVE A LIVING ROOM OF NOT LESS THAN |
| | 220 SQUARE FEET (20.4 M2) OF FLOOR AREA. AN ADDITIONAL |
| | 100 SQUARE FEET (9.3 M2) OF FLOOR AREA SHALL BE |
| | PROVIDED FOR EACH OCCUPANT OF SUCH UNIT IN EXCESS OF |
| | TWO. |
| | 2. THE UNIT SHALL BE PROVIDED WITH A SEPARATE CLOSET. |
| | 3. THE UNIT SHALL BE PROVIDED WITH A KITCHEN SINK, |
| | COOKING APPLIANCE AND REFRIGERATION FACILITIES, EACH |
| | HAVING A CLEAR WORKING SPACE OF NOT LESS THAN 30 INCHES |
| | (762 MM) IN FRONT. LIGHT AND VENTILATION CONFORMING TO |
| | THIS CODE SHALL BE PROVIDED. |
| | 4. THE UNIT SHALL BE PROVIDED WITH A SEPARATE BATHROOM |
| | CONTAINING A WATER CLOSET, LAVATORY AND BATHTUB OR |
| | SHOWER. |
| | |
| | 2B) PLEASE PROVIDE ADDITIONAL INFORMATION AS TO WHAT |
| | THESE TWO ROOMS ARE FOR, (1) BETWEEN ROOMS 10 & 11 AND |
| | (2) THE BATHROOM ADJACENT TO UNIT # 21. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) THE COVERSHEET DOES NOT DISCLOSE IF THIS IS A FIRE |
| | SPRINKLERED BUILDING, UNDER THE 2010 FBC EXISTING |
| | BUILDING CODE SECTION 904.1 . THE COVERSHEET DOES NOT |
| | DISCLOSE IF THIS IS A FIRE SPRINKLERED BUILDING, UNDER |
| | THE 2010 FBC EXISTING BUILDING CODE SECTION 904.1 FIRE |
| | PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY |
| | WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE |
| | OF OCCUPANCY CLASSIFICATION. |
| | |
| | 912.1.2 FIRE PROTECTION AND INTERIOR FINISH. |
| | THE PROVISIONS OF SECTIONS 912.2 AND 912.3 FOR FIRE |
| | PROTECTION AND INTERIOR FINISH, RESPECTIVELY, SHALL |
| | APPLY TO ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | 912.2 FIRE PROTECTION SYSTEMS. |
| | FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE |
| | WITH SECTIONS 912.2.1 AND 912.2.2. |
| | |
| | |
| | 3A) 912.2.1 FIRE SPRINKLER SYSTEM. |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. |
| | |
| | 2010 FBC-B F] 903.2.8 GROUP R. AN AUTOMATIC SPRINKLER |
| | SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3 SHALL |
| | BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A GROUP R |
| | FIRE AREA. |
| | |
| | 2010 FBC-B[F] 903.3 INSTALLATION REQUIREMENTS. |
| | AUTOMATIC SPRINKLER SYSTEMS SHALL BE DESIGNED AND |
| | INSTALLED IN ACCORDANCE WITH SECTIONS 903.3.1 THROUGH |
| | 903.3.6. |
| | |
| | 2010 FBC-B [F] 903.3.1 STANDARDS. |
| | SPRINKLER SYSTEMS SHALL BE DESIGNED AND INSTALLED IN |
| | ACCORDANCE WITH SECTION 903.3.1.1, UNLESS OTHERWISE |
| | PERMITTED BY SECTIONS 903.3.1.2 AND 903.3.1.3. |
| | |
| | |
| | 3B) 912.2.2 FIRE ALARM AND DETECTION SYSTEM. |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION |
| | APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT |
| | THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A |
| | FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL |
| | BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED. |
| | |
| | 2010 FBC-B [F] 907.2.9 GROUP R-2. |
| | FIRE ALARM SYSTEMS AND SMOKE ALARMS SHALL BE INSTALLED |
| | IN GROUP R-2 OCCUPANCIES AS REQUIRED IN SECTIONS |
| | 907.2.9.1 AND 907.2.9.2. |
| | [F] 907.2.9.1 MANUAL FIRE ALARM SYSTEM. |
| | A MANUAL FIRE ALARM SYSTEM THAT ACTIVATES THE OCCUPANT |
| | NOTIFICATION SYSTEM IN ACCORDANCE WITH SECTION 907.5 |
| | SHALL BE INSTALLED IN GROUP R-2 OCCUPANCIES WHERE: |
| | 1. ANY DWELLING UNIT OR SLEEPING UNIT IS LOCATED THREE |
| | OR MORE STORIES ABOVE THE LOWEST LEVEL OF EXIT |
| | DISCHARGE; |
| | 2. ANY DWELLING UNIT OR SLEEPING UNIT IS LOCATED MORE |
| | THAN ONE STORY BELOW THE HIGHEST LEVEL OF EXIT |
| | DISCHARGE OF EXITS SERVING THE DWELLING UNIT OR |
| | SLEEPING UNIT; OR |
| | 3. THE BUILDING CONTAINS MORE THAN 11 DWELLING UNITS OR |
| | SLEEPING UNITS. |
| | SEE EXCEPTIONS |
| | F] 907.2.9.2 SMOKE ALARMS. SINGLE- AND MULTIPLE-STATION |
| | SMOKE ALARMS SHALL BE INSTALLED IN ACCORDANCE WITH |
| | SECTION 907.2.11. |
| | [F] 907.2.11 SINGLE- AND MULTIPLE-STATION SMOKE ALARMS. |
| | LISTED SINGLE- AND MULTIPLE-STATION SMOKE ALARMS |
| | COMPLYING WITH UL 217 SHALL BE INSTALLED IN ACCORDANCE |
| | WITH SECTIONS 907.2.11.1 THROUGH 907.2.11.4 AND NFPA 7 |
| | |
| | 4) 912.3 INTERIOR FINISH. |
| | IN AREAS OF THE BUILDING UNDERGOING THE CHANGE OF |
| | OCCUPANCY CLASSIFICATION, THE INTERIOR FINISH OF WALLS |
| | AND CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING FOR THE NEW OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | |
| | |
| | 5) 905.1 GENERAL. MEANS OF EGRESS IN PORTIONS OF |
| | BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH SECTION 912.912.4.2 |
| | MEANS OF EGRESS FOR CHANGE OF USE TO EQUAL OR LOWER |
| | HAZARD CATEGORY.WHEN A CHANGE OF OCCUPANCY |
| | CLASSIFICATION IS MADE TO AN EQUAL OR LESSER HAZARD |
| | CATEGORY (HIGHER NUMBER) AS SHOWN IN TABLE 912.4, |
| | EXISTING ELEMENTS OF THE MEANS OF EGRESS SHALL COMPLY |
| | WITH THE REQUIREMENTS OF SECTION 805 FOR THE NEW |
| | OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR |
| | CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 5A) 805.3 EXIT SIGNS. MEANS OF EGRESS FROM THE HIGHEST |
| | WORK AREA FLOOR TO THE FLOOR OF EXIT DISCHARGE SHALL BE |
| | PROVIDED WITH EXIT SIGNS IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING |
| | |
| | 5B) 912.4.4 HANDRAILS. EXISTING STAIRWAYS SHALL COMPLY |
| | WITH THE HANDRAIL REQUIREMENTS OF SECTION 705.9 IN THE |
| | AREA OF THE CHANGE OF OCCUPANCY CLASSIFICATION. |
| | 705.9 HANDRAILS. |
| | THE REQUIREMENTS OF SECTIONS 705.9.1 AND 705.9.2 SHALL |
| | APPLY TO HANDRAILS FROM THE WORK AREA FLOOR TO, AND |
| | INCLUDING, THE LEVEL OF EXIT DISCHARGE. |
| | |
| | 705.9.1 MINIMUM REQUIREMENT. |
| | EVERY REQUIRED EXIT STAIRWAY THAT IS PART OF THE MEANS |
| | OF EGRESS FOR ANY WORK AREA AND THAT HAS THREE OR MORE |
| | RISERS AND IS NOT PROVIDED WITH AT LEAST ONE HANDRAIL, |
| | OR IN WHICH THE EXISTING HANDRAILS ARE JUDGED TO BE IN |
| | DANGER OF COLLAPSING, SHALL BE PROVIDED WITH HANDRAILS |
| | FOR THE FULL LENGTH OF THE RUN OF STEPS ON AT LEAST ONE |
| | SIDE. ALL EXIT STAIRWAYS WITH A REQUIRED EGRESS WIDTH |
| | OF MORE THAN 66 INCHES (1676 MM) SHALL HAVE HANDRAILS |
| | ON BOTH SIDES. |
| | |
| | 705.9.2 DESIGN. |
| | HANDRAILS REQUIRED IN ACCORDANCE WITH SECTION 705.9.1 |
| | SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE |
| | PROVISIONS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | EXCEPTION: HANDRAILS BEING REPLACED IN PART MAY MATCH |
| | THE EXISTING DESIGN. |
| | |
| | 5C) 912.4.5 GUARDS. EXISTING GUARDS SHALL COMPLY WITH |
| | THE REQUIREMENTS IN SECTION 705.10 IN THE AREA OF THE |
| | CHANGE OF OCCUPANCY CLASSIFICATION. |
| | 705.10 GUARDS. |
| | THE REQUIREMENTS OF SECTIONS 705.10.1 AND 705.10.2 |
| | SHALL APPLY TO GUARDS FROM THE WORK AREA FLOOR TO, AND |
| | INCLUDING, THE LEVEL OF EXIT DISCHARGE BUT SHALL BE |
| | CONFINED TO THE EGRESS PATH OF ANY WORK AREA. |
| | |
| | 705.10.1 MINIMUM REQUIREMENT. |
| | EVERY OPEN PORTION OF A STAIR, LANDING, OR BALCONY THAT |
| | IS MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR OR |
| | GRADE BELOW AND IS NOT PROVIDED WITH GUARDS, OR THOSE |
| | PORTIONS IN WHICH EXISTING GUARDS ARE JUDGED TO BE IN |
| | DANGER OF COLLAPSING, SHALL BE PROVIDED WITH GUARDS. |
| | |
| | 705.10.2 DESIGN. |
| | GUARDS REQUIRED IN ACCORDANCE WITH SECTION 705.10.1 |
| | SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE |
| | PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY. |
| | EXCEPTION: GUARDS BEING REPLACED IN PART MAY MATCH THE |
| | EXISTING DESIGN. |
| | |
| | |
| | 6) 906.1 ACCESSIBILITY IN PORTIONS OF BUILDINGS |
| | UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL |
| | COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, ACCESSIBILITY. |
| | 912.8 ACCESSIBILITY. EXISTING BUILDINGS THAT UNDERGO A |
| | CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL |
| | COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, ACCESSIBILITY. |
| | |
| | 2010 FL ACCESSIBILITY CODE: 202.4.1 DISPROPORTIONATE |
| | COST. |
| | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | |
| | 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF |
| | DISPROPORTIONALITY. |
| | WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| | OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| | ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| | ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| | FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| | ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| | ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |