2014-01-23 18:56:37 | BUILDING PLAN REVIEW |
| PERMIT: 14010891 |
| ADD: 1801 PALM BEACH LAKES RMU'S RETAIL MERCHANT UNITS |
| CONT: EMJ |
| TEL: (561)373-3902 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: THURSDAY JAN. 23/ 2014 |
| ACTION: DENIED |
| |
| 1) THE SITE PLAN SHOW RMU'S THROUGH OUT THE SITE AS |
| WELL AS KIOSK UNITS. THE PERMIT APPLICATION UNDER THE |
| WORK DESCRIPTION INDICATES" RMU/ KIOSK FOR VENDORS. |
| IT WOULD APPEAR THERE IS A DIFFERENCE IN UNITS AND SIZE |
| OF UNITS LOOKING AT THE PARTIAL SITE PLANS. 2010 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, ADMINISTRATION, 2010 EDITION SECTION |
| 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. THANK |
| YOU. |
| |
| 2) THERE ARE NO SPECIFICATIONS ON THESE UNITS, MUST |
| MEET THE 2010 FBC-B SECTION 402.11 KIOSKS. |
| KIOSKS AND SIMILAR STRUCTURES (TEMPORARY OR PERMANENT) |
| SHALL MEET THE FOLLOWING REQUIREMENTS: |
| |
| 1. COMBUSTIBLE KIOSKS OR OTHER STRUCTURES SHALL NOT BE |
| LOCATED WITHIN THE MALL UNLESS CONSTRUCTED OF ANY OF |
| THE FOLLOWING MATERIALS: |
| |
| 1.1. FIRE-RETARDANT-TREATED WOOD COMPLYING WITH SECTION |
| 2303.2. |
| |
| 1.2. FOAM PLASTICS HAVING A MAXIMUM HEAT-RELEASE RATE |
| NOT GREATER THAN 100 KILOWATTS (105 BTU/H) WHEN TESTED |
| IN ACCORDANCE WITH THE EXHIBIT BOOTH PROTOCOL IN UL |
| 1975. |
| |
| 1.3. ALUMINUM COMPOSITE MATERIAL (ACM) MEETING THE |
| REQUIREMENTS OF CLASS A INTERIOR FINISH IN ACCORDANCE |
| WITH CHAPTER 8 WHEN TESTED AS AN ASSEMBLY IN THE |
| MAXIMUM THICKNESS INTENDED FOR USE. |
| |
| 2. KIOSKS OR SIMILAR STRUCTURES LOCATED WITHIN THE MALL |
| SHALL BE PROVIDED WITH APPROVED FIRE SUPPRESSION AND |
| DETECTION DEVICES. |
| |
| 3. THE MINIMUM HORIZONTAL SEPARATION BETWEEN KIOSKS OR |
| GROUPINGS THEREOF AND OTHER STRUCTURES WITHIN THE MALL |
| SHALL BE 20 FEET (6096 MM). |
| |
| 4. EACH KIOSK OR SIMILAR STRUCTURE OR GROUPINGS THEREOF |
| SHALL HAVE A MAXIMUM AREA OF 300 SQUARE FEET (28 M2). |
| |
| 3) PLEASE PROVIDE HOW THESE UNITS WILL MEET WIND |
| LOADING AND THE RESISTANCE FOR OVERTURNING? 2010 FBC-B |
| 1609.6.4.1 MAIN WIND-FORCE-RESISTING SYSTEMS. |
| THE MWFRS SHALL BE INVESTIGATED FOR THE TORSIONAL |
| EFFECTS IDENTIFIED IN ASCE 7 FIGURE 27.4-8. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |