| 2014-06-04 11:34:41 | PLUMBING PLAN REVIEW |
| | PERMIT: 14010860 |
| | ADD: 2500 METROCENTRE BLVD SUITE # 1 |
| | CONT: TO BE DETERMINED |
| | TEL: (561)786-486-9513 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. JULY 04/2014 |
| | ACTION: PLUMBING PROVISO |
| | |
| | TOTAL SQ FOOTAGE OF BUILDING 17,973 SQ FT |
| | DAYCARE OCCUPANCY 4911 SQ FT APPROX |
| | BLDG TYPE 3B |
| | |
| | 1) DRINKING FOUNTAINS 2 REQUIRED, 2010 FL ACCESS CODE |
| | 211.3 MORE THAN MINIMUM NUMBER. |
| | WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING |
| | FOUNTAINS SPECIFIED IN 211.2 ARE PROVIDED, 50 PERCENT |
| | OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED |
| | SHALL COMPLY WITH 602.1 THROUGH 602.6, AND 50 PERCENT |
| | OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED |
| | SHALL COMPLY WITH 602.7. |
| | |
| | 602.1 GENERAL.DRINKING FOUNTAINS SHALL COMPLY WITH 307 |
| | AND 602. |
| | |
| | 602.2 CLEAR FLOOR SPACE.UNITS SHALL HAVE A CLEAR FLOOR |
| | OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A |
| | FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE |
| | CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| | EXCEPTION: A PARALLEL APPROACH COMPLYING WITH 305 SHALL |
| | BE PERMITTED AT UNITS FOR CHILDREN?S USE WHERE THE |
| | SPOUT IS 30 INCHES (760 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND AND IS 31/2 INCHES (90 MM) MAXIMUM FROM |
| | THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS. |
| | |
| | 602.3 OPERABLE PARTS.OPERABLE PARTS SHALL COMPLY WITH |
| | 309. |
| | |
| | 602.4 SPOUT HEIGHT.SPOUT OUTLETS SHALL BE 36 INCHES |
| | (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 602.5 SPOUT LOCATION.THE SPOUT SHALL BE LOCATED 15 |
| | INCHES (380 MM) MINIMUM FROM THE VERTICAL SUPPORT AND 5 |
| | INCHES (125 MM) MAXIMUM FROM THE FRONT EDGE OF THE |
| | UNIT, INCLUDING BUMPERS. |
| | |
| | 602.6 WATER FLOW.THE SPOUT SHALL PROVIDE A FLOW OF |
| | WATER 4 INCHES (100 MM) HIGH MINIMUM AND SHALL BE |
| | LOCATED 5 INCHES (125 MM) MAXIMUM FROM THE FRONT OF THE |
| | UNIT. THE ANGLE OF THE WATER STREAM SHALL BE MEASURED |
| | HORIZONTALLY RELATIVE TO THE FRONT FACE OF THE UNIT. |
| | WHERE SPOUTS ARE LOCATED LESS THAN 3 INCHES (75 MM) OF |
| | THE FRONT OF THE UNIT, THE ANGLE OF THE WATER STREAM |
| | SHALL BE 30 DEGREES MAXIMUM. WHERE SPOUTS ARE LOCATED |
| | BETWEEN 3 INCHES (75 MM) AND 5 INCHES (125 MM) MAXIMUM |
| | FROM THE FRONT OF THE UNIT, THE ANGLE OF THE WATER |
| | STREAM SHALL BE 15 DEGREES MAXIMUM. |
| | |
| | 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. |
| | SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING |
| | PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 |
| | INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |