| Date |
Text |
| 2014-01-16 12:28:25 | PERMIT #14010854 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PER NFPA 13: CHAPTER 8 | | | 8.15.20.1* IN NEW INSTALLATIONS EXPECTED TO SUPPLY | | | SPRINKLERS BELOW A CEILING, MINIMUM 1 IN. (25 MM) | | | OUTLETS SHALL BE PROVIDED. | | | 8.15.20.2* IN NEW INSTALLATIONS, IT SHALL BE PERMITTED | | | TO PROVIDE MINIMUM 1 IN. (25 MM) OUTLETS WITH HEXAGONAL | | | BUSHINGS TO ACCOMMODATE SPRINKLERS ATTACHED DIRECTLY TO | | | BRANCH LINE FITTINGS TO ALLOW FOR FUTURE SYSTEM | | | MODIFICATIONS. | | | 8.15.20.4.2 ALL PIPING OTHER THAN THE NIPPLE PERMITTED | | | IN 8.15.20.4.1 AND 8.15.20.4.3 SHALL BE A MINIMUM OF 1 | | | IN. (25 MM) IN DIAMETER. | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE SUBMITTED BY EMAIL ([email protected]) | | | ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND | | | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT | | | 500 NORTH DIXIE HIGHWAY. | | | | | | | | | SUE ELLEN CALDERON | | | FIRE INSPECTOR & INVESTIGATOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|