| Plan Review Notes For Permit 14010812 |
| Permit Number |
14010812 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-03-11 15:39:49 | THE FOLLOWING ITEMS WERE INITIALLY REQUESTED, BUT WERE | | | NOT ADDRESSED CORRECTLY IN THE RESUBMITTAL: | | | 1. THE SCOPE OF THIS PERMIT IS TO INSTALL A 36KW STAND | | | BY GENERATOR TO A 300 AMP SERVICE VIA A LOAD SHED | | | TRANSFER SWITCH. IN ORDER TO NOT OVERLOAD THE GENERATOR | | | THE EXISTING LOAD IS BEING DIVIDED INTO TWO (2) 150 AMP | | | PANELS. I ASKED FOR THE EC TO PROVIDE LOAD CALCS FOR | | | THE WORK (EACH SUB-PANEL) TO VERIFY ADEQUACY OF | | | GENERATOR FOR THIS LOAD. WHAT WAS SUBMITTED WERE | | | INCOMPLETE LOAD CALC FOR A SINGLE PANEL, THUS NOT | | | SHOWING THE COMPLETE LOAD ON THE GENERATOR. | | | 2. I ASKED FOR A CORRECTED RISER DIAGRAM INDICATING THE | | | WIRING FOR THE CONTACTORS AND LSM. THE CONTRACTOR SEEMS | | | TO BELIEVE THAT IS REQUIRED, SO I WANT TO SEE HOW WILL | | | THE TWO PANELS WILL BE SEPARATELY CONNECTED TO THE | | | TRANSFER SWITCH. | | | |
|