2014-02-21 10:08:56THIS APPLICATION FAILED THE ELECTRICAL REVIEW FOR THE
 FOLLOWING:
 1. TWO (2) SETS OF DRAWINGS ARE REQUIRED.
 2. THE SUBMITTED LOAD CALCS ARE BASED ON A SINGLE PHASE
 SERVICE OF 208 VAC RATHER THAN THE 240 VAC. (THIS WORKS
 IN YOUR FAVOR BY REDUCING THE CONNECTED LOAD)
 3. CORRECT YOUR RISER DIAGRAM TO INCLUDE THE CONTACTORS
 AND WIRING REQUIRED FOR THE LSM
 4. INCLUDE IN THE RISER DIAGRAM THE GAS LINE BONDING AS
 PER NEC 250.104(B)
 5. PROVIDE AN ELEVATION OF THE RESIDENCE FOR THE SIDE
 WHERE THE UNIT IS TO BE INSTALLED TO SHOW THAT THERE
 ARE NO OPENINGS TO THE HOME WITHIN TEN (10) FT. OF THE
 GENERATOR.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  