| Plan Review Notes For Permit 14010812 |
| Permit Number |
14010812 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-22 13:33:03 | THE SUBMITTED PLANS ARE NOT LEGIBLE AND ARE INCOMPLETE. | | | ADDITIONALLY, THERE IS AN ONGOING PERMIT 13071145 WITH | | | AN ELECTRICAL DESIGN WHICH MUST BE REVISED TO | | | ACCOMODATE THIS INSTALLATION. PLEASE PROVIDE THE | | | FOLLOWING: | | | 1) ELECTRICAL RISER DIAGRAM SHOWING MEANS OF TRANSFER( | | | ATS OR MTS), INSTALLATION AND GROUNDING | | | 2) LOAD CALUCULATIONS PER NEC 702 AS APPLICABLE, AND | | | PANEL SCHEDULES | | | 3) MANUFACTURERS SPEC SHEET FOR GENERATOR AND TRANSFER | | | SWITCH | | | 4) LOCATION OF ANY OPENINGS INTO THE DWELLING WITHIN | | | 10' OF GENERATOR | | | 5) SOURCE OF FUEL TO GENERATOR AND GAS RISER DIAGRAM OR | | | INDICATION THAT A SEPARATE DESIGN WILL BE SUBMITTED BY | | | FUTURE PERMIT APPLICATION. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|