| 2014-01-22 18:12:06 | |
| | 1) VALUE IS LOW FOR THE AMOUNT OF WORK TO BE COMPLETED |
| | UNDER THE SCOPE OF THIS PERMIT. HOLD WILL BE PUT OM |
| | PERMIT UNTILS FEES ARE INCREASED. |
| | |
| | W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| | ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| | AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| | A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) EGRESS PATHS CAN NOT BE CHECKED ON PLANS WILL BE |
| | REVIEWED COMPLIANCE WITH 2010 FBC-B 1017.3 AISLE |
| | ACCESSWAYS IN MERCANTILE OCCUPANCIES. |
| | |
| | 3) PLANS DO NOT SHOW ACCESSIBLE AISLES 2010 FL |
| | ACCESSIBILITY CODE 403.5.1. |
| | |
| | 4) PLANS DO NOT PROVIDE ENOUGH INFORMATION AS TO IF |
| | EITHER TENANT SPACE WILL REQUIRE DRESSING ROOMS, IF IF |
| | SO THEN COMPLIANCE WITH 2010 FL ACCESSIBILITY CODE |
| | 903.4.1-5. |
| | |
| | 5) PLANS ALSO FAIL TO PROVIDE COMPLIANCE WITH 2010 FL |
| | ACCESSIBILITY CODE 904.3.2 ,904.4.1-2. |
| | |
| | 6) THE BASE BUILDING (SHELL) PERMIT # 12100555 NOR DOES |
| | THE LATEST REVISION # 13120864 TO THE SHELL PERMIT EVEN |
| | SHOW A TENANT SPACE E244, THIS IS A NEW TENANT |
| | SEPERATION WALL. PLANS SHOW THE WALL TO BE A ONE HOUR |
| | FIRE RATING, PLEASE PROVIDE A DETAIL FOR THE 1 HOUR |
| | FIRE RATED WALL, PLEASE PROVIDE COMPLIANCE WITH |
| | 2010 FBC-B 709.4 CONTINUITY AND EITHER PROVIDE THE UL |
| | LISTING OR GYPSUM ASSOCIATION LISTING. |
| | |
| | JAMES A. WITMER CBO |