| Plan Review Notes For Permit 14010716 |
| Permit Number |
14010716 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-02-27 12:09:55 | ISSUED WITH PROVISO: | | | ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED. | | | NEC 210.12 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE | | | RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A | | | FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED | | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC | | | R313 | | | KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI PROTECTED. | | | NEC 210.8 | | | GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND | | | REAR ELEVATIONS. NEC 210.8 | | | PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH | | | CIRCUITS. NEC 210.52 | | | PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS. | | | NEC 210.11 (C)(3) | | | THE LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR LIGHT | | | AND SWITCH CONTROLLED OUTSIDE LIGHTS. NEC 210.70 | | | | | | | | | RL |
|