Plan Review Notes
Plan Review Notes For Permit 14010716
Permit Number 14010716
Review Stop B
Sequence Number 1
Notes
Date Text
2014-02-06 09:08:37RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR ROOF SHINGLES. NOA 11-0223.11
 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE
 CURRENT NOA. VISIT THE MIAMI-DADE WEBSITE AND DOWNLOAD
 CURRENT NOA.
  
 2- CLEARLY SPECIFY EXISTING BEDROOM WINDOW TYPE AND
 SIZE AND PROPOSED WINDOW TYPE AND SIZE TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. R310 OF
 2010 FBC-RESIDENTIAL.
  
 3- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 OF 2010
 FBC-ENERGY CONSERVATION.
  