| Plan Review Notes For Permit 14010707 |
| Permit Number |
14010707 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-02-27 13:14:19 | ISSUED WITH PROVISO | | | | | | LOCATION OF NEW PANEL SHALL OBSERVE REQUIRED SAFETY | | | CLEARANCES. NEC 110.26 | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE | | | RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A | | | FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED | | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC | | | R313 | | | | | | KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI PROTECTED. | | | NEC 210.8 | | | | | | GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND | | | REAR ELEVATIONS. NEC 210.8 | | | | | | PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS. | | | NEC 210.11 (C)(3) | | | | | | THE LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR LIGHT | | | AND SWITCH CONTROLLED OUTSIDE LIGHTS. NEC 210.70 | | | | | | ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 | | | FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 | | | FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 | | | | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | | | | |
|