Plan Review Notes
Plan Review Notes For Permit 14010707
Permit Number 14010707
Review Stop E
Sequence Number 2
Notes
Date Text
2014-02-27 13:14:19ISSUED WITH PROVISO
  
 LOCATION OF NEW PANEL SHALL OBSERVE REQUIRED SAFETY
 CLEARANCES. NEC 110.26
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
  
 KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI PROTECTED.
 NEC 210.8
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND
 REAR ELEVATIONS. NEC 210.8
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 NEC 210.11 (C)(3)
  
 THE LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR LIGHT
 AND SWITCH CONTROLLED OUTSIDE LIGHTS. NEC 210.70
  
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
  
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  