Plan Review Notes
Plan Review Notes For Permit 14010707
Permit Number 14010707
Review Stop E
Sequence Number 1
Notes
Date Text
2014-02-18 12:38:0114010707
 1402 7TH STREET
 REHABILITATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 THE SCOPE OF THE PROPOSED ELECTRICAL WORK IS NOT CLEAR.
 PROVIDE A DETAILED ELECTRICAL PLAN FOR ALL
 IMPROVEMENTS.
  
 INDICATE THE SIZE, RATING, LOCATION OF THE NEW ELECTRIC
 SERVICE, MAIN DISCONNECT AND PANEL BOARD. SHOW SERVICE
 AND PANEL BOARD LOCATIONS. SHOW NEW AND EXISTING
 OUTLETS. INCLUDE A PANEL SCHEDULE WITH SUMMARY LOAD
 CALCULATION. NEC 215.5
  
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED.
 NEC 210.12
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
  
 SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI
 PROTECTED. NEC 210.8
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND
 REAR ELEVATIONS. NEC 210.8
  
 PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH
 CIRCUITS. NEC 210.52
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 NEC 210.11 (C)(3)
  
 THE LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR LIGHT
 AND SWITCH CONTROLLED OUTSIDE LIGHTS. NEC 210.70
  
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
  
 A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE
 GROUND NEC 250.94
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  