| Plan Review Notes For Permit 14010630 |
| Permit Number |
14010630 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-27 10:11:22 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. IMPACT PROTECTION REQUIRED FBC 1609.1.4. NON IMPACT | | | WINDOWS ARE PROPOSED FOR THE THIRD FLOOR PER A-1.0, BUT | | | IMPACT WINDOWS PROPOSED ON ELEVATIONS A2.0. FIXED | | | WINDOWS SPECIFIED ON A2.0, SINGLE HUNG PROPOSED ON | | | A1.0. NATURE OF WORK PROPOSED NOT CLEAR, PLEASE | | | CORRELATE. IF NON IMPACT WINDOWS ARE PROPOSED, SEE THE | | | FOLLOWING DOCUMENT, ITEM 13, PAGE 6 REGARDING USE OF | | | REMOVABLE SHUTTERS ON MULTI STORY BUILDINGS: | | | | | | HTTP://WPB.ORG/DEVELOPMENT/CONSTRUCTION/PDF/WIND-BORNE_ | | | DEBRIS_IMPLEMETATION.PDF | | | | | | 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, | | | FAC9N-3. PRODUCT APPROVALS TO BE REVIEWED BY DESIGNER | | | OF RECORD PRIOR TO SUBMITTAL FBC 107. | | | | | | |
|