Plan Review Notes
Plan Review Notes For Permit 14010472
Permit Number 14010472
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2014-05-23 10:07:291835 OKEECHOBEE ROAD
 PERMIT #14010472
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT - SHEET A1.2: INDICATE THE COMMODITIES
 THAT WILL BE STORED (FLOOR AND RACKING SYSTEM) AND THE
 INTENDED HEIGHT OF STORAGE. NOTE: STORAGE EXCEEDING 12
 FEET IN ELEVATION IS CONSIDERED HIGH-PILED STORAGE AND
 MAY REQUIRE SPECIAL SPRINKLER PROTECTION.
  
 REPEAT COMMENT - SHEET A3.1: PANIC HARDWARE WILL BE
 REQUIRED ON ALL NEW AND EXISTING EXIT AND EXIT ACCESS
 DOORS DUE TO THE ASSEMBLY OCCUPANT LOAD EXCEEDING 100
 PERSONS (50 PERSONS PER FBC) AND USING THE MIXED
 NON-SEPARATED OCCUPANCY DESIGN (PER THE COVER SHEET
 DESCRIPTION). IF SEPARATED OCCUPANCIES ARE DESIRED, THE
 ASSEMBLY AND BUSINESS OCCUPANCIES WOULD BE PROHIBITED
 FROM HAVING TO EXIT THROUGH THE STORAGE OCCUPANCY AS IS
 CURRENTLY SHOWN.
  
 REPEAT COMMENT - GENERAL: PER SECTION 8.3.2.4, EACH
 FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS
 OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 REPEAT COMMENT - GENERAL: NO FIRE PROTECTION
 ENGINEERING DOCENTS SUBMITTED. FOR ISSUANCE OF A
 GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE
 FLORIDA BUILDING CODE REQUIRES SEALED FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF
 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 REPEAT COMMENT - DEMO: PROVIDE DRAWING NOTE INDICATING
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 REPEAT COMMENT - DEMO: PROVIDE DRAWING NOTE INDICATING,
 "FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730