| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | REPEAT COMMENT - SHEET A1.2: INDICATE THE COMMODITIES |
| | THAT WILL BE STORED (FLOOR AND RACKING SYSTEM) AND THE |
| | INTENDED HEIGHT OF STORAGE. NOTE: STORAGE EXCEEDING 12 |
| | FEET IN ELEVATION IS CONSIDERED HIGH-PILED STORAGE AND |
| | MAY REQUIRE SPECIAL SPRINKLER PROTECTION. |
| | |
| | REPEAT COMMENT - SHEET A3.1: PANIC HARDWARE WILL BE |
| | REQUIRED ON ALL NEW AND EXISTING EXIT AND EXIT ACCESS |
| | DOORS DUE TO THE ASSEMBLY OCCUPANT LOAD EXCEEDING 100 |
| | PERSONS (50 PERSONS PER FBC) AND USING THE MIXED |
| | NON-SEPARATED OCCUPANCY DESIGN (PER THE COVER SHEET |
| | DESCRIPTION). IF SEPARATED OCCUPANCIES ARE DESIRED, THE |
| | ASSEMBLY AND BUSINESS OCCUPANCIES WOULD BE PROHIBITED |
| | FROM HAVING TO EXIT THROUGH THE STORAGE OCCUPANCY AS IS |
| | CURRENTLY SHOWN. |
| | |
| | REPEAT COMMENT - GENERAL: PER SECTION 8.3.2.4, EACH |
| | FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS |
| | OR STENCILING READING FIRE BARRIER-PROTECT ALL |
| | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN |
| | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE |
| | SPACED NOT MORE THAN 15 FEET ON CENTER. |
| | |
| | REPEAT COMMENT - GENERAL: NO FIRE PROTECTION |
| | ENGINEERING DOCENTS SUBMITTED. FOR ISSUANCE OF A |
| | GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE |
| | FLORIDA BUILDING CODE REQUIRES SEALED FIRE PROTECTION |
| | CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF |
| | 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA |
| | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | REPEAT COMMENT - DEMO: PROVIDE DRAWING NOTE INDICATING |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| | SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR |
| | AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL |
| | HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS |
| | PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL |
| | BE PROVIDED. |
| | |
| | REPEAT COMMENT - DEMO: PROVIDE DRAWING NOTE INDICATING, |
| | "FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING |
| | (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE |
| | FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY." |
| | |