| 2014-01-17 11:19:19 | 1835 OKEECHOBEE ROAD |
| | PERMIT #14010472 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET A1.2: INDICATE THE COMMODITIES THAT WILL BE |
| | STORED (FLOOR AND RACKING SYSTEM) AND THE INTENDED |
| | HEIGHT OF STORAGE. NOTE: STORAGE EXCEEDING 12 FEET IN |
| | ELEVATION IS CONSIDERED HIGH-PILED STORAGE AND MAY |
| | REQUIRE SPECIAL SPRINKLER PROTECTION. |
| | |
| | SHEET A3.1: PANIC HARDWARE WILL BE REQUIRED ON ALL NEW |
| | AND EXISTING EXIT AND EXIT ACCESS DOORS DUE TO THE |
| | ASSEMBLY OCCUPANT LOAD EXCEEDING 100 PERSONS (50 |
| | PERSONS PER FBC) AND USING THE MIXED NON-SEPARATED |
| | OCCUPANCY DESIGN (PER THE COVER SHEET DESCRIPTION). IF |
| | SEPARATED OCCUPANCIES ARE DESIRED, THE ASSEMBLY AND |
| | BUSINESS OCCUPANCIES WOULD BE PROHIBITED FROM HAVING TO |
| | EXIT THROUGH THE STORAGE OCCUPANCY AS IS CURRENTLY |
| | SHOWN. |
| | |
| | SHEET FA2.1: NO FIRE ALARM NOTIFICATION APPLIANCE |
| | LOCATED AT THE SOUTHEAST AREA OF THE SPACE. |
| | |
| | GENERAL: PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL |
| | BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING |
| | READING FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | GENERAL: NO FIRE PROTECTION ENGINEERING DOCENTS |
| | SUBMITTED. FOR ISSUANCE OF A GENERAL BUILDING PERMIT, |
| | SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE |
| | REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS |
| | FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC |
| | FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE |
| | SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |
| | DEMO: PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION |
| | AND DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | DEMO: PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION |
| | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| | BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |
| | |
| | |