2014-01-17 11:19:191835 OKEECHOBEE ROAD
 PERMIT #14010472
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1.2: INDICATE THE COMMODITIES THAT WILL BE
 STORED (FLOOR AND RACKING SYSTEM) AND THE INTENDED
 HEIGHT OF STORAGE. NOTE: STORAGE EXCEEDING 12 FEET IN
 ELEVATION IS CONSIDERED HIGH-PILED STORAGE AND MAY
 REQUIRE SPECIAL SPRINKLER PROTECTION.
  
 SHEET A3.1: PANIC HARDWARE WILL BE REQUIRED ON ALL NEW
 AND EXISTING EXIT AND EXIT ACCESS DOORS DUE TO THE
 ASSEMBLY OCCUPANT LOAD EXCEEDING 100 PERSONS (50
 PERSONS PER FBC) AND USING THE MIXED NON-SEPARATED
 OCCUPANCY DESIGN (PER THE COVER SHEET DESCRIPTION). IF
 SEPARATED OCCUPANCIES ARE DESIRED, THE ASSEMBLY AND
 BUSINESS OCCUPANCIES WOULD BE PROHIBITED FROM HAVING TO
 EXIT THROUGH THE STORAGE OCCUPANCY AS IS CURRENTLY
 SHOWN.
  
 SHEET FA2.1: NO FIRE ALARM NOTIFICATION APPLIANCE
 LOCATED AT THE SOUTHEAST AREA OF THE SPACE.
  
 GENERAL: PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL
 BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING
 READING FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 GENERAL: NO FIRE PROTECTION ENGINEERING DOCENTS
 SUBMITTED. FOR ISSUANCE OF A GENERAL BUILDING PERMIT,
 SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE
 REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS
 FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC
 FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 DEMO: PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION
 AND DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 DEMO: PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved