| Plan Review Notes For Permit 14010438 |
| Permit Number |
14010438 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-03 17:26:29 | NOTICE TO FIRE ALARM CONTRACTOR: | | | PRIOR TO FINAL ELECTRICAL INSPECTION, THIS SYSTEM SHALL | | | UNDERGO A REACCEPTANCE TEST AS PER NFPA 72, SECTION | | | 10.4.1.2. RECORDS OF SUCH SHALL BE KEPT IN THE SYSTEM | | | LOG AS REQUIRED. | | | NOTICE: | | | ALL LOW VOLTAGE & CONTROL OR COMMUNICATION WIRING SHALL | | | BE LISTED FOR THE APPLICATION | | | |
|