| 2014-01-14 12:00:28 | PLUMBING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561 |
| | |
| | 2010 FLORIDA PLUMBING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: TUESDAY JAN. 14/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK |
| | LIST THE INSTALATION OF A 750 GALLON GREASE |
| | INTERCEPTOR. CIVIL SHEETS WERE INCLUDED SHOWING THE |
| | LOCATION OF THE GREASE INTERCEPTOR, C-7 SHOWS THE |
| | SIZING TO THE CITY ENGINEERING STANDARD BUT NO |
| | INFORMATION WAS SUBMITTED IN REGARDS TO COMPLIANCE WITH |
| | SIZING OF THE GREASE INTERCEPTOR TO THE REQUIREMENTS OF |
| | THE 2010 FBC-PLUMBING SECTION TABLE 1003.5.1 EITHER; |
| | A) SIZING FORMULA FOR RESTARAUNTS |
| | OR |
| | B) OTHER ESTABLISHMENTS WITH COMMERCIAL KITCHENS. |
| | |
| | THESE PLANS WERE PREPARED BY ALBEERTO Z. ZUNIGA P. E. |
| | AND CALCULATIONS SHALL ALSO BE DESIGNED BY SAID |
| | ENGINEER OR THERE DELIGATE. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |