| Plan Review Notes For Permit 14010350 |
| Permit Number |
14010350 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-28 20:05:10 | AS PER THE MANUFACTURER, THESE UNITS REQUIRE A 100 AMP | | | SERVICE EACH. YOU SHALL SUBMIT A RISER DIAGRAM | | | INDICATING WHERE THE SOURCE OF ELECTRIC POWER WILL BE | | | OBTAINED FROM. IF THE SERVICE WILL BE MOUNTED ON A SELF | | | SUPPORTING STAND, PROVIDE ENGINEERING TO MEET THE | | | MINIMUM WIND LOADS. |
|