Plan Review Notes
Plan Review Notes For Permit 14010350
Permit Number 14010350
Review Stop E
Sequence Number 1
Notes
Date Text
2014-01-28 20:05:10AS PER THE MANUFACTURER, THESE UNITS REQUIRE A 100 AMP
 SERVICE EACH. YOU SHALL SUBMIT A RISER DIAGRAM
 INDICATING WHERE THE SOURCE OF ELECTRIC POWER WILL BE
 OBTAINED FROM. IF THE SERVICE WILL BE MOUNTED ON A SELF
 SUPPORTING STAND, PROVIDE ENGINEERING TO MEET THE
 MINIMUM WIND LOADS.