| 2014-03-26 17:41:51 | MECHANICAL PLAN REVIEW |
| | PERMIT: 14010226 |
| | ADD: 319 CLEMATIS ST SUITE # 112 |
| | CONT: CLAY KOHLMEYER |
| | TEL: (561) 627-3190 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. MARCH 26/2014 |
| | |
| | MECHANICAL PROVISO: |
| | |
| | 1) HOOD TO BE REVIEWED UNDER A SEPARATE PERMIT WITH |
| | PLANS. |
| | |
| | 2)MECHANICAL APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 2A) PROVIDE PRODUCT APPROVALS FOR THE A/C CONDENSATE |
| | STAND PER RULE 9N-3 FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: (31)(G PRE-ENGINEERED A/C STANDS. |
| | |
| | 2B) FANSKSF-1 & KEF-1 PROVIDE CURB DETAILS, ATTACHMENT |
| | DETAILS AND ASSOCIATED PRESSURES. |
| | |
| | PLUMBING PROVISO: |
| | |
| | 1) A SEPARATE PERMIT IS REQUIRED FOR A GREASE |
| | INTERCEPTOR. PROVIDE A CURRENT SIZING METHOD 2010 FBC-P |
| | 1003.3.4 FOR THE GREASE INTERCEPTOR. PDI G101 |
| | TABLE A1.7 IS NO LONGER CURRENT, NOT SINCE THEY DID |
| | UPDATES IN 2006. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |