| Plan Review Notes For Permit 14010226 |
| Permit Number |
14010226 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-04 16:13:21 | PLAN DENIED | | | 1) FRESH AIR CALCULATION REQUIRED ON THE PLAN | | | PER TABLE 403.3 FBC (M) 2010 | | | 2) HOOD AND COOLERS REQUIRE SEPARATE APPLICATION | | | PLAN AND PERMIT. | | | 3) EQUIPMENT SCHEDULE REQUIRED ON THE PLAN. | | | 4) ENERGY CALCULATION REQUIRED PER SECTION | | | 301.2 ENERGY UTILIZATION 2010 FBC (M) | | | 5) PROVIDE A DETAIL ON THE PLAN FROM THE ENGINEER | | | FOR THE CONDENSER STAND TO ROOF TIE DOWN AND | | | CONDENSER TO STAND TIE DOWN PER SECTION | | | 301.12 WIND RESISTANCE. 2010 FBC (M) | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|