| 2014-01-14 17:56:52 | THESE PLANS WERE CONDITIONALLY APPROVED AS FOLLOWS: | | | (A TIP TO THE CONTRACTOR) IT IS IN YOUR BEST INTEREST | | | TO WAIT TILL ALL THE REVIEWS ARE COMPLETED BEFORE YOU | | | SUBMIT A CORRECTION. THE RE-SUBMITTAL WOULD HAVE FAILED | | | FOR THE ITEM NOTED, AND THE PLANS WOULD HAVE HAD TO BE | | | RESUBMITTED WHEN CORRECTED. I WILL NOT DO THIS NEXT | | | TIME) | | | AS STATED IN NFPA 72 2007 EDITION SECTION 5.13.6, THE | | | MANUAL PULL STATIONS SHALL BE WITHIN 5 FT. OF THE DOOR. |
|