| Plan Review Notes For Permit 14010182 |
| Permit Number |
14010182 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-06 17:39:24 | 2010 FBC | | | | | | 1) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE FLAT | | | ROOF AS REQUIRED BY DCA RULE 9N-3. INDICATE THE | | | APPROVED ASSEMBLY AND ITS MAXIMUM DESIGN PRESSURE ON | | | PRODUCT APPROVAL. PROVIDE TWO COPIES OF SIGNED AND | | | SEALED RAS 117 CALCULATIONS FOR ENHANCED FASTENING IF | | | THE MAXIMUM DESIGN PRESSURES FOR THE SPECIFIED ASSEMBLY | | | IS TOO LOW FOR THE CORNER AND PERIMETER AREAS. THIS | | | STRUCTURE HAS A 15 FT MEAN ROOF HEIGHT, IS LOCATED IN A | | | 170 MPH VULT WINDSPEED AND EXPOSURE CATEGORY B. THE | | | UPLIFT PRESSURES ARE - 31.3 PSF, -52.5 PSF AND -79.1 | | | PSF FOR ROOF ZONES 1, 2 AND 3 RESPECTIVELY. | | | | | | 2) THE VALUE FOR THE WORK WAS INCREASED FROM $2400.00 | | | TO $ 4321.00 BASED ON MARSHALL- SWIFT VALUATION DATA. | | | CITY AMENDMENTS 109.3 THE OWNER'S AND CONTRACTOR'S | | | NOTARIZED SIGNATURES ARE REQUIRED ON THE PERMIT | | | APPLICATION BEFORE PERMIT ISSUANCE. A RECORDED COPY OF | | | THE NOTICE OF COMMENCEMENT IS REQUIRED BEFORE THE FIRST | | | INSPECTION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|