| Notes |
| Date |
Text |
| 2014-01-08 17:13:27 | 2010 FBC | | | | | | REVISION DENIED BY BUILDING | | | | | | 1) NOTE #7 ON THE DRAWING FROM TURQUOISE ENGINEERING | | | SPECIFIES A SIMPSON LTT19 STRAP ANCHORED THROUGH THE | | | TOP PLATE INTO THE TIE BEAM WITH A 1/2" X 4" TITEN | | | ANCHOR. THIS IS DESIGNED AND TESTED AS TENSION STRAP | | | AND THE TENSION VALUE IS THE ONLY ONE THAT IS PROVIDED. | | | THE LTT19 STRAP IS NOT DESIGNED TO BE USED TO ANCHOR | | | ROOF TRUSSES, WHICH ARE REQUIRED TO RESIST LATERAL | | | LOADS IN ADDITION TO UPLIFT. SPECIFY A CONNECTOR THAT | | | HAS BEEN DESIGNED, TESTED AND APPROVED TO USED TO | | | ANCHOR ROOF TRUSSES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|