| 2014-01-03 16:59:01 | 2010 FBC | | | | | | REVISION DENIED BY BUILDING | | | | | | 1) PROVIDE THE VALUE FOR THE INCREASED SCOPE OF WORK, | | | INCLUDE DESIGN COSTS. CITY AMENDMENTS 109.3 | | | | | | 2) THE ROOF FRAMING REPAIR DETAIL DRAWINGS FROM RIZA N. | | | ALTAN, PE # 38521. BECAUSE HE IS NOT THE DESIGNER OF | | | RECORD FOR THIS PROJECT, HIS DRAWINGS WILL NEED TO HAVE | | | A SHOP DRAWING REVIEW STAMP FROM THE DESIGNER OF | | | RECORD, ROBERT F. SONBERG, AR #6280 OR A LETTER FROM | | | HIM DELEGATING THE SCOPE OF WORK SHOWN IN THE | | | ENGINEER'S DRAWINGS TO HIM. FS 471, 481 AND CITY | | | AMENDMENTS 107.1 | | | | | | 3) NOTE #7 ON THE DRAWING FROM TURQUOISE ENGINEERING | | | REQUIRES BENDING A SIMPSON ST18 STRAP 90 DEGREES AND | | | ANCHORING IT THROUGH THE TOP PLATE INTO THE TIE BEAM | | | WITH A TAPCON. THIS IS NOT AN ACCEPTABLE APPLICATION | | | FOR THIS STRAP. PLEASE SPECIFY A CONNECTOR THAT HAS | | | BEEN DESIGNED, TESTED AND APPROVED FOR THE SPECIFIC | | | APPLICATION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|