| Plan Review Notes For Permit 13121174 |
| Permit Number |
13121174 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-08 14:44:35 | REVISION REQUIRED | | | 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLAN | | | PER TABLE 403.3 FBC (M) 2010 | | | 2) SHOW FRESH AIR DUCT ON THE PLAN. PER | | | SECTION 107 FBC 2010 | | | 3) REFER TO SECTION 503.2.4.4 SHUTOFF | | | DAMPER CONTROLS FLORIDA ENERGY CODE 2010 | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|