| Plan Review Notes For Permit 13121113 |
| Permit Number |
13121113 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-30 20:00:27 | THE FOLLOWING ELECTRICAL CORRECTIONS HAVE TO BE MADE TO | | | THE SUBMITTED DRAWINGS: | | | 1. INDICATE FROM WHICH OF THE THREE TRANSFORMER SHOWN | | | ON THE PLANS IS THE SERVICE IN QUESTION BEING SERVED. | | | 2. INDICATE IF THE FEEDERS ARE OVERHEAD OR UNDERGROUND, | | | THE DRAWING LEADS ME TO BELIEVE THESE ARE TRANSFORMER | | | PADS ON THE GROUND, AND THE RISER DIAGRAM REFLECTS | | | SERVICE FROM OVERHEAD. | | | 3. THERE IS A CONFLICT BETWEEN ELECTRICAL NOTE 5 AND | | | THE RISER DIAGRAM. | | | 4. THE RISER DIAGRAM APPEARS TO VIOLATE THE | | | REQUIREMENTS OF NEC 300.5(B) | | | 5. INDICATE ON THE PLANS THE INTENDED WIRING METHOD | | | APPLIED TO SERVE THE NEW RECEPTACLES. |
|