Plan Review Notes
Plan Review Notes For Permit 13121113
Permit Number 13121113
Review Stop E
Sequence Number 1
Notes
Date Text
2013-12-30 20:00:27THE FOLLOWING ELECTRICAL CORRECTIONS HAVE TO BE MADE TO
 THE SUBMITTED DRAWINGS:
 1. INDICATE FROM WHICH OF THE THREE TRANSFORMER SHOWN
 ON THE PLANS IS THE SERVICE IN QUESTION BEING SERVED.
 2. INDICATE IF THE FEEDERS ARE OVERHEAD OR UNDERGROUND,
 THE DRAWING LEADS ME TO BELIEVE THESE ARE TRANSFORMER
 PADS ON THE GROUND, AND THE RISER DIAGRAM REFLECTS
 SERVICE FROM OVERHEAD.
 3. THERE IS A CONFLICT BETWEEN ELECTRICAL NOTE 5 AND
 THE RISER DIAGRAM.
 4. THE RISER DIAGRAM APPEARS TO VIOLATE THE
 REQUIREMENTS OF NEC 300.5(B)
 5. INDICATE ON THE PLANS THE INTENDED WIRING METHOD
 APPLIED TO SERVE THE NEW RECEPTACLES.