| Plan Review Notes For Permit 13121099 |
| Permit Number |
13121099 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-04-28 13:48:38 | PER NFPA 72, SECTION 4.4, THE DEDICATED FIRE ALARM | | | CIRCUIT BREAKER SHALL BE MARKED IN RED AND IDENTIFIED | | | AS ?FIRE ALARM CIRCUIT? AND BE MECHANICALLY | | | PROTECTED.NOTICE TO FIRE ALARM CONTRACTOR: | | | ALL DOCUMENTATION AS REQUIRED PER NFPA 72 SECTION 4.5 | | | SHALL BE PROVIDED UPON COMPLETION AND BE AVAILABLE FOR | | | FINAL INSPECTION. | | | |
|