| Plan Review Notes For Permit 13121076 |
| Permit Number |
13121076 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-02-21 17:01:05 | PLUMBING PLAN REVIEW | | | PERMIT: 13121076 | | | ADD: 8151 OKEECHOBEE BLVD | | | CONT: P & T CONSTRUCTION | | | TEL: (561)324-8055 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | ARCHITECT: TERCILLA COURTEMANCHE 561-478-4457 | | | RENE TERCILLA | | | | | | RGD CONSULTING ENGINEERS 561-743-0165 | | | P. E. MICHAEL J. BISHOP | | | | | | 1ST REVIEW | | | DATE: TUES. JAN. 28/2014 | | | ACTION: PASSED | | | | | | INFORMATIONA ONLY,L NO RESPONCE REQUIRED. THE GREASE | | | TRAP INFORMATION HAS BEEN PROVIDED ON SHEET P6.2 FOR | | | SIZING BUT WILL REQUIRE A SEPERATE PERMIT. | | | INFORMATION PROVIDED ON SIZING; | | | MARK: GT-1 SCHIER MODEL PATG-30-LO INDOOR | | | UNIT MAX FLOW RATE 30 | | | LIQUID CAP. 23 GALLONS | | | MAX. GREASE CAPACITY 90 POUNDS | | | 3" INLET & OUTLET | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|